Quick Installation Guide for Solar Power Inverter M125HV EU V1 EN 2019-04-01
Grounding via the PE screw of the AC con-
nection
Cable lug selection
► Use copper cable lugs covered with tin for copper cables.
Use aluminum cables cable lugs covered with tin for alumi-
num cables.
► Always follow the cable lug manufacturer’s installation
instructions.
∅
10,5
max. 31
∅
10.5
max. 31
1. Screw the earthing cable to the PE screw (torque: 25 Nm).
M10 screw, spring washer and washer are already
mounted on the inverter.
2. Perform a continuity check of the grounding connection.
Grounding the inverter housing