Installation Instructions for the Hybrid E5 Battery Storage System EU V1 EN 2018-09-17
Connecting the communication card of the inverter
Overview
Data format
Baud rate
9600, 19200, 38400; standard: 19200
Data bits
8
Stop bit
1
Parity
Not applicable
The baud rate can be set on the inverter display after com-
missioning.
Cable requirements
● Shielded twisted-pair cable with solid conductors
(CAT 5 or CAT 6.
● Cable diameter: 5 mm
● Wire cross-section: 0.25 ... 1.5 mm
2
Lay the cable with a suitable clearance to the AC and DC
cables to prevent interference in the data connection.
DIP switch for the RS485 termination resistor
1
VCC (+12 V; 0.5 A)
2
RS485 termination resistor
Digital inputs and external power-off (EPO)
To control the active power, an external ripple control
receiver can be connected to the digital inputs.
Pin Short circuit
Assigned action
VCC -
-
INV
OFF VCC + INV OFF
External shutdown (E-Power
off, EPO)
K1
VCC + K1
Max. active power 0%
K2
VCC + K2
Max. active power 30 %
K3
VCC + K3
Max. active power 60 %
Pin Short circuit
Assigned action
K4
VCC + K4
Max. active power 100 %
K5
VCC + K5
Reserved
K6
VCC + K6
Reserved
After commissioning, the relays for the external power-off
can be defined on the display as normally closed or nor-
mally open relays.
Dry contact
The inverter has one dry contact. The contact is closed
when the relays energize.
Event
Description
Disabled
The functions for the dry contact are
switched off.
On Grid
Inverter is connected to the mains
grid.
Insulation
Insulation error.
Alarm
An error, failure or warning message
is present.
Error
An error message is present.
Fault
A failure message is present.
Warning
A warning message is present.
An event can be assigned to the dry contacts can be set
on the inverter display after commissioning.
The default setting for both contacts is "Disabled".