Delta Dual V4/V6 (DMS-217/079)

Installation Instructions

For Ground Water Applications

T.

E.

W.

Summary of Contents for Dual V4

Page 1: ...01992 523523 info deltamembranes com www deltamembranes com Delta Dual V4 V6 DMS 217 079 Installation Instructions For Ground Water Applications T E W ...

Page 2: ...ded herein must neither be distributed copied reproduced edited or processed for any other purpose nor otherwise transmitted published or made available to a third party without express written consent from Delta Membranes Subject to technical modification without prior notice Delta Membranes 2015 ...

Page 3: ... B2 Connecting perimeter channel to chamber 12 Section B3 Connecting perimeter channel via a 1 5 40mm inlet pipe 13 Section C Connecting discharge and cable duct 14 Section D1 Backfill around chamber with concrete RC Box 16 Section D2 Backfill around chamber with concrete Ground 17 Section D3 Backfill around chamber with concrete Reinforced cage 18 Section E Installing pumps and high level alarm i...

Page 4: ...ctors with competent building plumbing and electrical skills The pumps operate by fixed arm floats the duty pump is set at a standard height 210mm to base of float and the backup pump is set at a high level 380mm to base of float The high level alarm where fitted will operate if the duty pump fails leaving the backup pump to discharge water A high level alarm DMS 270 is offered as a recommended ex...

Page 5: ...10mm to 2 BSP Female Thread including 1 25 Male Iron DMS 0151 Saddle Clamp 160mm to 2 BSP Female Thread including 1 25 Male Iron DMS 0152 2 Pipe Clip DMS 059 500ml PVC Solvent Cement DMS 0158 Name Company Name Property Address Email Phone No Mobile No A selection of discharge pipework and fittings are available for the Dual V4 V6 pump station Should you require to place an order for any of these i...

Page 6: ...sement Slab 5 0 Spare Parts Part Description Part No 1 V4 V6 Pump c w 1 1 1 2 DMS 216 084 1 1 Float Switch Assembly DMS 344 1 2 Non return Valve DMS 328 2 Discharge Arm DMS 326 3 O Ring DMS 132 4 1 25 Brass Gate Valve DMS 329 5 Connector Piece DMS 338 6 Connector Adaptor DMS 337 7 2 Non pressure Male Iron DMS 335 8 Y piece c w 2 O rings DMS 321 1 2 3 8 4 5 6 7 7 1 1 1 2 6 For technical support ple...

Page 7: ...r Material High Density Polyethnylene ICO1314 grade Size mm Chamber Diameter 660 Overall Diameter 902 across spigots Depth 800 Volume L Below Inlet 137 Total 273 Inspection Cover Not supplied Clear opening to chamber mm 310 x 310 Fixed Inlets 3 x 110 160mm Cable Duct mm 50 Vent N A Discharge Connection 2 50mm BSP Female External to chamber Internal Pipework Manifold 1 25 32mm BSP Class C RCBO Rati...

Page 8: ... pump chamber installed more than 500mm below floor finishes cannot be serviced safely in accordance with CDM regulations If the inlet does not allow the pump chamber to be within depth limits please contact PPS on 01279 757400 to discuss chamber options Delta Dual V4 V6 8 For technical support please call 01279 757400 ...

Page 9: ...tion either during or after installation Please read these instructions carefully prior to installing the chamber If there is anything that is unclear our technical help desk is available on 01279 757400 9 0 Pump Station Location This station requires routine maintenance therefore it is important that careful consideration is taken to position the chamber in a location that allows permanent access...

Page 10: ...work to protrude into RC box by a minimum of 100mm 1 3 11 0 Installation of Chamber Section A Install re bar as per structural engineer s drawings Pour concrete to form RC box as per structural engineer s drawings 2 4 Construction of reinforced concrete box Delta Dual V4 V6 10 For technical support please call 01279 757400 ...

Page 11: ...cket end s where inlet pipe s are to be connected Fit push fit coupler 5 7 Position chamber in RC box 6 Connecting 110mm pipework Connect inlet pipework to the required chamber spigot 8 Delta Dual V4 V6 For technical support please call 01279 757400 11 ...

Page 12: ...r Section B2 Drill holes in the corners inside the area marked in red Insert the perimeter channel into the chamber allowing 35mm of overhang inside the chamber 10 12 Connecting perimeter channel to chamber To be followed when installing perimeter channel directly into upper side of chamber Delta Dual V4 V6 12 For technical support please call 01279 757400 ...

Page 13: ...Saw off 110mm socket end s to be used 13 15 Cut 40mm pipe to length allowing an overhang of 35mm inside the chamber 14 Connecting perimeter channel via a 1 5 40mm inlet pipe Attach a DMS 341 adaptor to the 40mm pipe and connect the adaptor to the chamber via a 110mm push fit coupler 16 Delta Dual V4 V6 For technical support please call 01279 757400 13 ...

Page 14: ...st 20mm of the external face of the discharge and cable duct pipe and internal side of their respective male iron 17 19 Screw the high pressure male iron into the female iron Push discharge and cable duct pipe into their respective male iron twisting the pipe as it is pushed into the male iron to remove any trapped air 18 20 Delta Dual V4 V6 14 For technical support please call 01279 757400 ...

Page 15: ...tion of Chamber Section C cont Ensure a draw cord is pulled through the cable duct as the cable duct is built 21 Connecting discharge and cable duct Delta Dual V4 V6 For technical support please call 01279 757400 15 ...

Page 16: ...hen installing chamber in an RC box Check all pipes are connected to the chamber correctly Fill void between RC box and chamber with concrete min C35 grade or as per engineer s drawings 22 24 Completely fill chamber with water 23 Delta Dual V4 V6 16 For technical support please call 01279 757400 ...

Page 17: ... Section D2 Fill void between soil and chamber with concrete min C35 grade or as per engineer s drawings 26 Completely fill chamber with water 25 Backfill around chamber with concrete To be followed when installing chamber in the ground Allow concrete to cure 27 Delta Dual V4 V6 ...

Page 18: ...min C35 grade or as per engineer s drawings 29 Completely fill chamber with water 28 Backfill around chamber with concrete To be followed when installing chamber in the ground with a reinforced cage Allow concrete to cure 30 Delta Dual V4 V6 18 For technical support please call 01279 757400 ...

Page 19: ...e any debris from chamber and residual water using a wet vac 32 Remove discharge arms from Y piece manifold and screw Y piece on to gatevalve Ensure gatevalve is fully open 33 Wrap PTFE tape around thread located on male irons at the bottom of the discharge arms and screw discharge arms on to pumps 34 For technical support please call 01279 757400 19 ...

Page 20: ...e arms to Y piece manifold 36 Fill chamber half full with water 35 Installing pumps and high level alarm in chamber When installing a high level alarm refer to the high level alarm installation instructions 37 20 For technical support please call 01279 757400 Delta Dual V4 V6 Pull pump and high level alarm cables through cable duct 38 ...

Page 21: ...n chamber Isolate main supply and connect each pump and high level alarm cable to a separate non switched fused spur 39 Turn mains supply on and lift each pumps float arm to test water is discharging correctly 40 To test float switch refer to the high level alarm installation instructions 41 Re fit temporary site cover to protect the pump station 42 ...

Page 22: ...paratly For internal wiring of the high level alarm please see the high level alarm instruction manual Cable Length The pump and float switch is supplied with a 10m cable length When only using the standard 10m cable attached to pump the cable duct length should be no longer than 6m If the cable duct needs to be longer than 6m please follow the cable extension guide to select an appropriate cable ...

Page 23: ...posed to A first aid kit must be close to hand 15 0 Guarantee The Dual V4 V6 pump chamber comes with a 12 month component guarantee which covers any manufacturing faults and defects as a result of poor workmanship Pump chambers that have not been commissioned have a 12 month component guarantee from date of delivery Pump chambers that have been commissioned have a 12 month component guarantee from...

Page 24: ...nnecting to discharge arm Discharge pipe is blocked a drainage company is required Pump impellor is jammed turn off power and isolate pump remove pump from chamber unscrew pump base using Torx screwdriver and free impellor WARNING Insure mains power and pump is isolated before taking pump apart and seek advice from a qualified electrician Pump is tripping Pump is wired incorrectly or not on a sepa...

Page 25: ...check pump discharges in less than 40 seconds Check pipework is connected correctly look for leaks Check all cables are securely cable tied to manifold and clear of float switches Check each pump is wired to an individual 13A non switched spur Check each spur is wired to an individual 16A RCBO not RCD Label spurs using stickers provided Check power is on Check battery backup is switched on correct...

Page 26: ...17 0 Self Commissioning Please scan this commissioning form and email to service ppsgroupuk com Further comments Delta Dual V4 V6 ...

Page 27: ...For technical support please call 01279 757400 27 Delta Dual V4 V6 18 0 Notes ...

Page 28: ... of hours service Planned maintenance Factory trained engineers Unit 12 Haslemere Ind Est Pig Lane Bishop s Stortford CM23 3HG After Sales Service Precise Passionate Service 01279 757400 info ppsgroupuk com www ppsgroupuk com T E W All Delta Membrane pump systems are fitted can be maintained by our partners Packaged Pump Systems With our long term relationship we ensure that the system selected is...