TECHNICAL DATASHEET

 

CliQ DIN Rail Power Supply 

24 V 60 W 1 Phase / DRP024V060W1AZ

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (September 2021, Rev. 10) 

 

3

 

Mechanical 

 

Case Cover / Chassis 

 

Plastic 

Dimensions (L x W x D) 

 

120.6 x 32 x 113 mm (4.75 x 1.26 x 4.45 inch) 

Unit Weight 

 

0.33 kg (0.73 lb) 

Indicator 

Green LED  DC OK 

Cooling System 

 

Convection 

Terminal 

Input  3 Pins (Rated 300 V/20 A) 

 

Output  2 Pins (Rated 300 V/20 A) 

Wire 

  AWG 20-14 

Mounting Rail 

  Standard TS35 DIN Rail in accordance with EN 60715 

Noise (1 Meter from power supply) 

 

Sound Pressure Level (SPL) < 40 dBA 

 

 

Environment 

 

Surrounding Air Temperature 

Operating  -20°C to +80°C 

 

Storage  -25°C to +85°C 

Power De-rating 

Vertical Mounting  -10°C to -20°C output power is 80% of rated power, 

< 0°C de-rate power by 2% / °C, 

> 50°C de-rate power by 2.5% / °C 

 

Horizontal Mounting  -10°C to -20°C output power is 80% of rated power, 

< 0°C de-rate power by 2% / °C, 

> 50°C de-rate power by 2.5% / °C, 

> 70°C de-rate power by 4% / °C 

Operating Humidity 

  5 to 95% RH (Non-Condensing) 

Operating Altitude 

  0 to 2,000 Meters (6,560 ft) 

Shock Test 

Non-Operating  IEC 60068-2-27, 30 G (300 m/S²) for a duration of 18 ms, 

1 time per direction, 6 times in total 

Vibration 

Non-Operating  IEC 60068-2-6, 10 Hz to 150 Hz @ 50 m/S² (5 G peak); 

90 min per axis for all X, Y, Z direction 

Over Voltage Category 

  III 

According to IEC/EN 62477-1 / EN 60204-1 

(clearance and creepage distances) and 

IEC 62103 (safety part) 

Pollution Degree 

  2 

 

 

Protections 

 

Overvoltage 

< 32 V, ±10%, SELV Output, Hiccup Mode, 

Non-Latching (Auto-Recovery) 

Overload / Overcurrent 

> 150% of rated load current, Hiccup Mode, 

Non-Latching (Auto-Recovery) 

Over Temperature 

< 80°C Surrounding Air Temperature @ 100% load, 

Non-Latching (Auto-Recovery) 

Short Circuit 

Hiccup Mode, Non-Latching 

(Auto-Recovery when the fault is removed) 

Internal Fuse at L pin 

T3.15AH 

Protection Against Shock 

Class I with PE* connection 

*PE: Primary Earth 

 

 

 

Summary of Contents for DRP024V060W1AZ

Page 1: ...companies Delta Electronics Group offers state of the art designs made to withstand harsh industrial environments Its rugged plastic casing has a compact body at only 32 mm which is both shock and vi...

Page 2: ...Nominal Output Voltage 24 Vdc Factory Set Point Tolerance 24 Vdc 2 Output Voltage Adjustment Range 22 28 Vdc Output Current 2 50 A continuously operating at 24 V 3 75 A Power Boost for 3 seconds at 2...

Page 3: ...l Mounting 10 C to 20 C output power is 80 of rated power 0 C de rate power by 2 C 50 C de rate power by 2 5 C 70 C de rate power by 4 C Operating Humidity 5 to 95 RH Non Condensing Operating Altitude...

Page 4: ...ltage SELV IEC 60950 1 Electrical Safety SIQ Bauart EN 62368 1 UL cUL recognized UL 60950 1 and CSA C22 2 No 60950 1 File No E191395 UL 62368 1 and CSA C22 2 No 62368 1 File No E191395 cCSAus CSA C22...

Page 5: ...ria A1 80 MHz 1GHz 3 V M 80 modulation 1kHz Electrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A1 2 kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mode2 2 kV Differential Mode3 2 kV Con...

Page 6: ...ecified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com September 2021 Rev 10 6 Block Diagram Device Description 1 Input terminal block connector 2 Output terminal block conne...

Page 7: ...t voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition 3 In order for...

Page 8: ...UL 62368 flexible cables require ferrules Use appropriate copper cables designed to sustain operating temperature of at least 75 C or more to fulfill UL requirements Dismounting Fig 2 1 Mounting Snap...

Page 9: ...o ensure sufficient clearance around the device Vertical Mounting 50 mm 1 97 inch above and below the device as well as a lateral distance of 20 mm 0 79 inch to other units Horizontal Mounting 50 mm 1...

Page 10: ...90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current is the pe...

Page 11: ...ted and approved on 20 A UL and 16 A IEC branch circuits without additional protection device An external protection device is only required if the supplying branch has an ampacity greater than above...

Page 12: ...rrent will operate in Hiccup mode as shown in the illustration in the OLP OCP section on this page The power supply will return to normal operation after the short circuit is removed Overvoltage Prote...

Page 13: ...stem load from Vout Please note that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60V to 0 90V Typical 0 65V depending on th...

Page 14: ...earth wire or to the machine ground Fig 7 2 of 3 Phase System Input Operation Connection Diagram 2 of 3 Phase System Input Operation Delta s CliQ can use on 2 of 3 phase system Please refer to the fol...

Page 15: ...for any claim or action arising from any error for the provided information in the datasheets Customer shall take its responsibility for evaluation of using the product before placing an order with De...

Reviews: