TECHNICAL DATASHEET
CliQ DIN Rail Power Supply
24 V 60 W 1 Phase / DRP024V060W1AZ
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (September 2021, Rev. 10)
9
Safety Instructions
Vertical Mounting
•
ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not turned
OFF, there is risk of explosion / severe damage.
•
To guarantee sufficient convection cooling, please refer to the following instructions to ensure sufficient clearance around
the device.
Vertical Mounting: 50 mm (1.97 inch) above and below the device as well as a lateral distance of 20 mm (0.79 inch) to other
units.
Horizontal Mounting: 50 mm (1.97 inch) above and below the device as well as a lateral distance of 50 mm (1.97 inch) to
other units.
•
Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power
supply. Risk of burns!
•
Only plug in and unplug connectors when power is turned off!
•
DO NOT insert any objects into the unit.
•
Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during
this time.
Horizontal Mounting