DNT-T221 (Rev 4.1) Installation Guide

 

Model Numbers 

 

Features 

DNT-T221 

DNT-H121B 

Internal Thermistor Input 

 

 

Internal Humitity Input 

 

 

Additional I/O 

2IP, 2AO, 1 BO 

1 IP, 2 AO, 1 BO 

Backlighting Option 

B

 

 

External Input Terminator 

Option 

X

 

 

Button Icons 

INT INT 

An appended button icon code must be included to specify the desired icons embossed on the buttons as 
follows: 

[

default

] Bottom 2 buttons are 

 and 

 (Setpoint Adjust), top 2 are 

OFF

 and 

ON

 

INT 

Bottom 2 buttons are 

 and 

 (Setpoint Adjust), top 2 are 

O

 and 

I

 – 

International

 

You need not specify button icons if you want the default, but must specify INT if you want the international 
button icons. (i.e., DNT-T221-INT). 
 

Package Contents 

 

• 

Delta Network Thermostat: BACstat II Product, 

DNT-T221 (Rev 4.1)

 

• 

DNT-T221 (Rev 4.1)

 Installation Guide 

 
 

Other Relevant Documents 

 

• 

Delta Controls Wiring and Installation Guidelines 

• 

BACstat II Application Guide (for Configuration & Programming) 

• 

ORCAview Operator Guide 

• 

ORCAview Technical Reference Manual 

• 

BACstat II, DAC and DCU Release Notes 

 

Product Specifications 

 

Power Requirements 

• 

24V AC, 50/60 Hz (Class 2) 

• 

15 VA maximum (with internally powered triac at full load) 
(3VA without triac loading) 

Ambient Ratings 

• 

32º to 131º F (0º to 55º C) 

• 

10 to 90% RH (non-condensing) 

 

 

Page 2 of 10

 

 

Document Edition 1.8

 

Summary of Contents for DNT-T221

Page 1: ...damper position and more When connected on a BACnet MS TP network the DNT T221 functions as an independent BACnet thermostat When connected to a controller on a LINKnet network it provides a programma...

Page 2: ...specify button icons if you want the default but must specify INT if you want the international button icons i e DNT T221 INT Package Contents Delta Network Thermostat BACstat II Product DNT T221 Rev...

Page 3: ...00 ohm 77 F 25 C Humidity Sensor DNT H121B Model Only Accuracy of 2 RH from 0 100 RH 25 C VSUPPLY 2 6Vdc Display Resolution of 0 1 Stability of 1 RH typical 50 RH over 5 years Note Extended exposure t...

Page 4: ...MS TP Connection Set via Keypad Configuration Setup or Software Setup Keypad MAC Address Range 1 to 99 per network segment Software Address Range As per the BACnet standard Supports DNA Delta s intuit...

Page 5: ...hermistor sensor or a remotely located Thermistor is connected to IP1 The diagram to the left shows the factory default selection of the Internal 10 K Thermistor External For connecting a remotely loc...

Page 6: ...use a wire nut to terminate all the outputs to GND 3 Ensure you use the recommended balanced cable for the network and follow the documented procedures within Delta Controls Wiring and Installation G...

Page 7: ...ced 100 to 120 nominal impedance Twisted Shielded Pair TSP Cable Nominal capacitance of 16 PF FT or lower Nominal velocity of propagation of 66 or higher Topology For MS TP and LINKnet networks ensure...

Page 8: ...SC 1212 H E DSC 1280 H E DSC T305 System Devices RS 485 NET1 NET2 NET1 NET2 RS 232 BACstat I BACstat II with No I O BACstat II with muxed I O I O Field Modules LINKnet Devices TRM Level 4 Network LINK...

Page 9: ...separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV te...

Page 10: ...4 2 1995 A1 1999 ESD Immunity ESD Immunity Level A Level A EN 61000 4 3 1996 EN 61000 4 3 1996 RF Electromagnetic Field Immunity RF Electromagnetic Field Immunity Level A Level A ENV 50204 1995 ENV 50...

Reviews: