DNT-T221 (Rev 4.1) Installation Guide

 

Network Topology 

 

1.  BACstats Configured as MS/TP Subnet Devices 

With V3.21 firmware or higher, one possible MS/TP network architecture has the MS/TP devices configured as 
Subnet devices, which allows BACstats to reside on the MS/TP network with other Subnet devices.  Note that 
V3.21 requires a DCU, while V3.22 or higher may use any System Controller instead. 

 

2.  BACstats Configured as LINKnet Devices 

The BACstat may reside on LINKnet instead of MS/TP.  However, this requires a controller that supports a 
LINKnet network for I/O expansion.  The maximum LINKnet devices with or without I/O depends on the 
controller.  All built-in applications must be disabled, but the I/O may be muxed (with V3.22 or higher 
firmware). 

 

DCU/DSC

(System Device)

BACnet (MS/TP) - Level 3 Network (Subnet)

DAC

(Subnet

Device)

TRM

DAC

(Subnet

Device)

TRM

Level 4 

Network 

(LINKnet)

 16x16 Controller
 12x12 Controller
 12x8 Controller
 6x6 Controller
 Room Controller
 VAV/VVT Controller
 Lighting Controller
 BACstat I
 BACstat II

  (with or without I/O)

 Input Field Modules

Subnet Devices

 DSC-1616EX [DCU]
 DSC-1616(H/E)
 DSC-1212(H/E)
 DSC-1280(H/E)
 DSC-T305

System Devices

RS-485

NET1

NET2

NET1

NET2

RS-232

 BACstat I
 BACstat II

  (with No I/O)

 BACstat II

  (with muxed I/O)

 I/O Field Modules

LINKnet Devices

TRM

Level 4 

Network 

(LINKnet)

LINKnet Notes:

1. Ensure you use the recommended 

balanced cable.

2. Ensure the cable is installed as a daisy-

chain from one device to the next. (1000' 
or 300m maximum).

3. *Ensure you jumper select a MS/TP 

termination resistor when you have more 
than 1 or 2 devices.

4. Depending on the controller, up to 12 

devices are supported on a LINKnet 
network, with limitations on how many of 
these may have I/O.  (Refer to the 
Technical Reference Manual.)

ORCAview 

OWS

DFM

Ethernet Note:

If the DCU or DSC has Ethernet capability, it may exist on an 
Ethernet network with other controllers in the same building, on which 
the ORCAview OWS could reside as well (instead of PTP).

PTP

MS/TP Notes:

1. Ensure you use the recommended balanced cable.
2. Ensure the cable is installed as a daisy-chain from one 

device to the next (4,000' or 1220m maximum).

3. *Ensure you jumper select a termination resistor on each 

end of each MS/TP network segment. 

4. The maximum nodes per MS/TP network is 50 without a 

repeater or up to 99 with at least one repeater (RPT-768).

Network Diagram 

 (with V3.22 Firmware)

* Note 3

 
 

 

Page 8 of 10

 

 

Document Edition 1.8

 

Summary of Contents for DNT-T221

Page 1: ...damper position and more When connected on a BACnet MS TP network the DNT T221 functions as an independent BACnet thermostat When connected to a controller on a LINKnet network it provides a programma...

Page 2: ...specify button icons if you want the default but must specify INT if you want the international button icons i e DNT T221 INT Package Contents Delta Network Thermostat BACstat II Product DNT T221 Rev...

Page 3: ...00 ohm 77 F 25 C Humidity Sensor DNT H121B Model Only Accuracy of 2 RH from 0 100 RH 25 C VSUPPLY 2 6Vdc Display Resolution of 0 1 Stability of 1 RH typical 50 RH over 5 years Note Extended exposure t...

Page 4: ...MS TP Connection Set via Keypad Configuration Setup or Software Setup Keypad MAC Address Range 1 to 99 per network segment Software Address Range As per the BACnet standard Supports DNA Delta s intuit...

Page 5: ...hermistor sensor or a remotely located Thermistor is connected to IP1 The diagram to the left shows the factory default selection of the Internal 10 K Thermistor External For connecting a remotely loc...

Page 6: ...use a wire nut to terminate all the outputs to GND 3 Ensure you use the recommended balanced cable for the network and follow the documented procedures within Delta Controls Wiring and Installation G...

Page 7: ...ced 100 to 120 nominal impedance Twisted Shielded Pair TSP Cable Nominal capacitance of 16 PF FT or lower Nominal velocity of propagation of 66 or higher Topology For MS TP and LINKnet networks ensure...

Page 8: ...SC 1212 H E DSC 1280 H E DSC T305 System Devices RS 485 NET1 NET2 NET1 NET2 RS 232 BACstat I BACstat II with No I O BACstat II with muxed I O I O Field Modules LINKnet Devices TRM Level 4 Network LINK...

Page 9: ...separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV te...

Page 10: ...4 2 1995 A1 1999 ESD Immunity ESD Immunity Level A Level A EN 61000 4 3 1996 EN 61000 4 3 1996 RF Electromagnetic Field Immunity RF Electromagnetic Field Immunity Level A Level A ENV 50204 1995 ENV 50...

Reviews: