43
☆
If drain hose cannot has enough drooping gradient, drain raising pipe should be added.
☆
To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m.
×
(wrong)
○
(Correct) 1/100 or more gradient
1-1.5m
☆
Use the drain hose and clamp attached. Insert
the drain hose to the drain vent, and then tighten
the clamp.
☆
Entwine the big sponge on the clamp of drain
hose to insulate heat.
☆
Heat insulation should be done to indoor drain
hose.
●
Note of drainage raising pipe
☆
The install height of the drain raising pipe should less than 280mm.
☆
The drain raising pipe should form a upright angle with the unit, and distance to unit should not
beyond 300mm.
Instruction
☆
The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t
has to endure the unnecessary outside force.
☆
Please install the drain hose according to the following process if several drain hoses join together.
bel
ow50
0mm
.
belo
w75
mm
Drain hose(attachment)
Below 4mm
Sponge(attachment)
Clamp(attachment)
Clamp
Drain hose
Sponge (gray)
4
3