HD35
- 116 -
V1.12
Address Type
Holding Register description
AP ED RE AL
10059
W
Relay #1 deactivation duration in seconds (1…54000 s) in case
of cyclical activation (Coils – address 18 = 0).
10060
W
Number of relay #1 activations in case of cyclical activation
(Coils – address 18 = 0).
10061
W
Relay #2 activation duration in seconds (1…54000 s) in case of
cyclical activation (Coils – address 21 = 0).
10062
W
Relay #2 deactivation duration in seconds (1…54000 s) in case
of cyclical activation (Coils – address 21 = 0).
10063
W
Number of relay #2 activations in case of cyclical activation
(Coils – address 21 = 0).
20000
to 20011
B
User code with ASCII codification of measurement #1.
Available for models with more measurements of the same type.
20012
to 20023
B
User code with ASCII codification of measurement #2.
Available for models with more measurements of the same type.
20024
to 20035
B
User code with ASCII codification of measurement #3.
Available for models with more measurements of the same type.
20036
to 20047
B
User code with ASCII codification of measurement #4.
Available for models with more measurements of the same type.
20048
to 20059
B
User code with ASCII codification of measurement #5.
Available for models with more measurements of the same type.
20060
to 20071
B
User code with ASCII codification of measurement #6.
Available for models with more measurements of the same type.
20072
to 20083
B
User code with ASCII codification of measurement #7.
Available for models with more measurements of the same type.
20084
to 20095
B
User code with ASCII codification of measurement #8.
Available for models with more measurements of the same type.
20096
to20107
B
User code with ASCII codification of measurement #9.
Available for models with more measurements of the same type.
20108
to 20119
B
User code with ASCII codification of measurement #10.
Available for models with more measurements of the same type.
20120
to 20131
B
User code with ASCII codification of measurement #11.
Available for models with more measurements of the same type.
20132
to 20143
B
User code with ASCII codification of measurement #12.
Available for models with more measurements of the same type.
Warning: the execution of MODBUS commands changing the parameters setting of a device
can take a certain time, due to the RF transmission between the device and the base unit. The
value of the flag PENDING_CONF (Discrete Inputs – address 2) is set to 1 during the execution
of a configuration change request. Only when the flag returns to 0 the request is considered as
concluded. The flag CMD_FAILURE (Coils – address 7) allows to check whether the request was
successful. It is recommended to check the status of the two flags before considering a device
configuration changed.