DeviceNet Remote I/O Communication Module RTU-DNET
DVP-PLC Application Manual
36
Attribute
ID
Access
rule
Name
Range
Default
Explanation
offline treatment
0: Ignored
1: Alarm
2: Stop DeviceNet IO
12 Get/Set
Special module
error treatment
0 ~ 2
1
How RTU-DNET will react when it
detects errors.
0: Ignored
1: Alarm
2: Stop DeviceNet IO
13 Get/Set
RTU-DNET
configuration
validation
N/A 0
Validating the configuration of
RTU-DNET when set to “11”.
14 Get/Set
Reset RTU-DNET
N/A
0
Resetting RTU-DENT when set to “10”.
After it, the parameter will change to “0”
automatically.
Common services
Implemented for
Service code
Class
Instance
Service name
0x0E Yes
Yes
Get_Attribute_Single
0x10 No
Yes
Set_Attribute_Single
Class 0x9B – Extension module setup parameter object
Class attribute
Attribute ID
Access rule
Name
Data type
1 Get Revision UINT
Instance 1 ~ 8 (parameters for the 1
st
~ 8
th
special modules)
Attribute
ID
Access
rule
Name
Range
Default
Explanation
1 Get
Model name
N/A
N/A
Model code for the special module
2 Get
Length of input data
N/A
N/A
The sum of the input data length of special
modules connected.
Unit: word
3 Get
Length of output
daat
N/A
N/A
The sum of the output data length of
special modules connected.
Unit: word
0
Special module online
b0
1
Special module offline
0
Special module normal
b1
1
Spcial module in error
0
Special module and
configuration consistent
b2
1
Special module and
configuration inconsistent
0
Configuration data valid
b3
1
Configuration data invalid
4
Get
Status
0 ~ 63
N/A
b4
0
Special module identifiable