DeviceNet Remote I/O Communication Module RTU-DNET
DVP-PLC Application Manual
6
2.3 DeviceNet Connection Port
The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with RTU-DNET.
PIN
Signal
Color
Content
1 V- Black
0
VDC
2 CAN_L Blue Signal-
3 SHIELD
-
Shielded
4 CAN_H White
5 V+ Red 24
VDC
1
2
3
4
5
2.4 RUN/STOP Switch
RUN/STOP action
Explanation
STOP
→
RUN
1. Re-detecting the extension module.
2. Reading/writing the data in the extension
module.
RUN
→
STOP
Stop reading/writing the data in the extension
module.
RUN
STOP
2.5 Address Switch
The switch is used on setting up the node address of RTU-DNET on DeviceNet. Range: 00 ~ 63 (64 ~ 99 are
forbidden).
Switch setting
Content
0 ~ 63
Valid DeviceNet node address
64 ~ 99
Invalid DeviceNet node address
9
1
6
4
5
0
0
9
1
3
2
7
8
2
5
6
4
3
7
8
Example: If you need to set the node address of RTU-DNET to 26, simply switch the corresponding switch of x10
1
to 2 and the corresponding switch of x10
0
to 6.
Note:
z
Please set up the node address when the power is switched off. After the setup is completed, re-power
RTU-DNET.
z
When RTU-DNET is operating, changing the setting of node address will be invalid.
z
Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.
2.6 Function Switch
The function switches are for:
z
Setting up data retention function (IN0)
z
Setting up the baud rate of DeviceNet (DR0 ~ DR1)
DR1
DR0
Baud rate
OFF OFF
125
kbps
OFF ON
250
kbps
ON OFF
500
kbps
ON ON
Incorrect
setting