background image

www.deltapowersolutions.com

Delta UPS - Amplon Family

User Manual

The power behind competitiveness

INX Series, Single Phase

1/ 2/ 3 kVA

Summary of Contents for INX-1K

Page 1: ...www deltapowersolutions com Delta UPS Amplon Family User Manual The power behind competitiveness INX Series Single Phase 1 2 3 kVA...

Page 2: ...s product Any disposition duplication dissemination reproduction modification translation extraction or usage of this Manual in whole or in part is prohibited without the prior written permission of D...

Page 3: ...1 Rear Panel View 4 2 2 Operating principle 6 2 3 Setup the UPS 6 2 4 Battery Replacement 9 Chapter 3 Operation 10 3 1 Button Operation 10 3 2 LCD Panel 11 3 3 Audible Alarm 13 3 4 LCD Display Wordin...

Page 4: ...install the UPS system near water or in moist environments z z Do not install the UPS system where it would be exposed to direct sunlight or near heater z z Do not block ventilation holes in the UPS...

Page 5: ...er foreign objects from inside of the UPS system 1 5 Maintenance Service and Faults z z The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personn...

Page 6: ...type of batteries z z Do not attempt to dispose of batteries by burning them This could cause battery explosion z z Do not open or destroy batteries Escaping electrolyte can cause injury to the skin a...

Page 7: ...l View z z Standard Runtime Model 1 kVA 2 kVA 3 kVA Chapter 2 Installation and Setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the...

Page 8: ...plon INX Series 1 kVA 2 kVA 3 kVA No Item 1 AC input 2 Input circuit breaker 3 USB port 4 RS 232 port 5 Mini slot 6 Output socket 7 External battery connector 8 Output terminal z z Extended Runtime Mo...

Page 9: ...ing principle of the UPS is shown as below 2 3 Setup the UPS Step 1 Connect battery wires If UPS is extended runtime model please connect external batteries as below chart Please refer to below chart...

Page 10: ...IA 2kVA Plug 16A INDIA 3kVA Plug 16A INDIA Step 3 UPS output connection z z For socket type outputs simply connect devices to the outlets z z For terminal type outputs please follow below steps for th...

Page 11: ...installing mini card in the UPS it will provide advanced communication and monitoring options NOTE 1 The USB port and RS 232 port can t work at the same time 2 If you choose to use the USB port rather...

Page 12: ...ware center php 2 4 Battery Replacement WARNING 1 This rack UPS is equipped with internal batteries and user can replace the batteries without shutting down the UPS or connected loads hot swappable ba...

Page 13: ...button to display previous selection in UPS setting mode z z Switch to UPS self test mode Press and hold this button for 5 seconds to enter UPS self testing while in AC mode ECO mode or converter mode...

Page 14: ...en pausing for 10 seconds z z Setting mode Press and hold this button for 5 seconds to enter UPS setting mode when the UPS is in standby mode or bypass mode z z Down key Press this button to display n...

Page 15: ...in details in 3 7 UPS Setting 3 Mute operation Indicates that the UPS alarm is disabled 4 Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltag...

Page 16: ...the battery is fault Indicates low battery level and low battery voltage 8 Input Battery voltage information Indicates the input voltage or frequency or battery voltage Vac Input voltage Vdc battery...

Page 17: ...4 LCD Display Wordings Index Abbreviation Display Content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter TP Temperature CH Charger FU Bypass frequency u...

Page 18: ...Parameter 3 are the setting options or values for each program z z 01 Output voltage setting Parameter 3 Output voltage For 200 208 220 230 240 VAC models you may choose the following output voltage 2...

Page 19: ...F DIS converter mode disable Default z z 03 Output frequency setting Parameter 2 3 Output frequency setting You may set the initial frequency in battery mode BAT 50 presents output frequency 50Hz BAT...

Page 20: ...ceptable high voltage point and low voltage point for ECO mode by pressing the Down key or Up key HLS High loss voltage in ECO mode in parameter 2 For 200 208 220 230 240 VAC models the setting range...

Page 21: ...ameter 2 3 Set the acceptable high voltage point and acceptable low voltage point for bypass mode by pressing the Down key or Up key HLS Bypass high voltage point For 200 208 220 230 240 VAC models 23...

Page 22: ...kup time will be only 10 seconds 999 When setting as 999 the backup time setting will be disabled Default z z 09 Total battery AH Parameter 3 Set up total battery AH value of the UPS unit AH 7 999 set...

Page 23: ...t The UPS will also charge the battery in online mode z z ECO Mode Energy saving mode When the input voltage is within voltage regulation range the UPS will run in bypass mode to supply power to outpu...

Page 24: ...e UPS is overloaded the UPS will enter bypass mode or bypass mode can be set via the front panel The alarm is sounding every 10 seconds z z Standby Mode The UPS is powered off and there is no output b...

Page 25: ...Alarm Low battery Sounding every second Overload Sounding twice every second Battery is not connected Sounding every second Over charge Sounding every second Over temperature Sounding every second Ch...

Page 26: ...e incorrectly con nected Check if all batteries are connected well Fault code is shown as 27 or 28 and the icon is lighting on the LCD display and the alarm is continuously sounding Battery voltage is...

Page 27: ...on the UPS output Check output wir ing and if connected devices are in short circuit status Fault code is shown as 01 02 03 04 11 12 13 41 or 45 on the LCD display and the alarm is continuously soundi...

Page 28: ...tact your dealer Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material z z Storage Before storing charge the UPS 5 hours St...

Page 29: ...or 57 63 Hz Synchronized Range Frequency Range Batt Mode 50Hz 0 25Hz or 60Hz 0 3Hz Overload Ambient Temp 35 C 105 110 The UPS shuts down after 10 minutes in bat tery mode or transfers to bypass when...

Page 30: ...Standard Runtime Model Dimensions D x W x H mm 282 X 145 X 220 504 X 145 X 220 421 X 190 X 318 Net Weight kg 9 0 16 5 25 Extended Runtime Model Dimensions D x W x H mm 282 x 145 x 220 397x 145 x 220 N...

Page 31: ...nce or irresistible force i e war fire natural disaster etc and this warranty also expressly excludes all incidental and consequential damages Maintenance service for a fee is provided for any damage...

Page 32: ......