04: ECO enable/ disable
Parameter 3:
Enable or disable ECO function. You may choose the following
two options.
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)
z
z
05: ECO voltage range setting
Parameter 2 & 3:
Set the acceptable high voltage point and low voltage point
for ECO mode by pressing the Down key or Up key.
HLS:
High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter
3 is from +7V to +24V of the nominal voltage.(Default: +12V)
LLS:
Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter
3 is from -7V to -24V of the nominal voltage. (Default: -12V)