27
Amplon INX Series
Model
1K
2K
3K
Battery
Battery Type
12 V / 9 AH
12 V / 9 AH
12 V / 9 AH
Numbers
Standard Runtime Model: 2/4/6 ;
Extended Runtime Model: 3/6/6
Recharge Time
Standard Runtime Model: 4 hours recover to 90%
capacity (Typical) ; Extended Runtime Model: Depends
on the batteries attached
Charging Current
Standard Runtime Model: 1A ;
Extended Runtime model: 1/2/4/6A
External Battery
Connector
Standard Runtime Model: N/A ;
Extended Runtime Model: 1pc
Physical
Standard Runtime Model
Dimensions
(D x W x H)
(mm)
282 X 145 X 220 504 X 145 X 220 421 X 190 X 318
Net Weight (kg)
9.0
16.5
25
Extended Runtime Model
Dimensions
(D x W x H)
(mm)
282 x 145 x 220
397x 145 x 220
Net Weight (kg)
4.4
7.3
7.8
Environment
Operation Humidity
20-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 50dBA @ 1 Meter
Communication
Interface
RS-232, USB, Mini-slot
NOTE :
1. * At 110~160Vac, linear de-rating between 60 ~ 100% load is required.
2. **De-rate capacity to 80% of capacity when the output voltage is adjusted to
200VAC or 208VAC
3. Please refer to the rating label for the safety rating.
4. All specifications are subject to change without prior notice.