Parameter
Explanation
Multiple
Max. timeout times
Trigger
Cyclic, changing status, application object
O
Æ
T packet interval
Packet interval between originator and target
T
Æ
O packet interval
Packet interval between originator and target
8 Modbus
Communication
8.1 Function Codes Supported
Function code
Explanation
Devices supported
0x02
Read discrete input
RX
0x03
Read holding register
BR, AL, MB, MW, MIP
0x06
Write single holding register
BR, AL, MB, MW, MIP
0x10
Write multiple holding register
BR, AL, MB, MW, MIP
0x17
Read/write multiple holding register
BR, AL, MB, MW, MIP
8.2 Exception Codes Supported
Exception code
Explanation
0x01 Illegal
function
0x02
Illegal data addresss
0x03
Illegal data value
0x04 Slave
device
failure
0x0A
Gateway path unavailable
0x0B
Gateway target device failed to respond
8.3 Device Type & Device Address
Discrete input
Device
type
Modbus address
(Hex)
5-digit Modbus address (Dec)
6-digit Modbus address
(Dec)
Number
RX
0x0400 ~ 0x0402
11025 ~ 11027
101025 ~ 101027
3
Holding register
Device
type
Modbus address
(Hex)
5-digit Modbus address (Dec)
6-digit Modbus address
(Dec)
Number
BR
0x0000 ~ 0x00FF
40001 ~ 40256
400001 ~ 400256
64
AL
0x0200 ~ 0x0202
40513 ~ 40515
400513 ~ 400515
3
X
0x0400 ~ 0x0402
41025 ~ 41027
401025 ~ 401027
3
IN
0x0500 ~ 0x05FF
41281 ~ 41536
401281 ~ 401536
256
OUT
0x0600 ~ 0x06FF
41537 ~ 41791
401537 ~ 401791
256
MB
0x2000 ~ 0x20FF
48193 ~ 48448
408193 ~ 408448
256
MW
0x2200 ~ 0x23FF
48705 ~ 49216
408705 ~ 409216
512
MIP
0x2400 ~ 0x24FF
49217 ~ 49471
409217 ~ 409471