Ethernet Communication Module IFD9507
DVP-PLC Application Manual
63
3. Select “Static” in IP Configuration.
4. Enter “192.168.1.99” in IP Address field.
5. Enter “255.255.255.0” in Netmask field.
6. Select “Ethernet/IP” in Application Protocol.
7. Enter “231” in Station Address.
8. Press
“OK”.
9. Open
DCISoft
“Ethernet/IP” configuration screen.
10. Enter AB PowerFlex 40P IP Address“192.168.1.72” in Dest IP Field.
11. Select “Cyclic” in Trigger.
12. Enter PowerFlex 40P parameter “1”,”4”,”2”,”2”,”2 byte”,”6” in In Instance, In Size, Out Instance, Out
Size, Width, Config Instance in turn.
13. Press “OK”.
WPL
program
1. Write control data to DVP IFD9507 IN register (H0500)
2. Use WPL MODWR instruction to write the control data to EIP (H0500).
3. Ex.
RUN
:
111000000011010
Æ
H701A
STOP
:
111000000011001
Æ
H7019
Reverse RUN
:
111000000101010
Æ
H702A
4. Select which communication index you want. Write 1~4 to DVPIFD9507 BR15 (H000F).
Use WPL MODWR instruction to select the DVP IFD9507 BR (H0500) index.
5. Set the I/O Enable Flag (BR14).
Summary of Contents for Ethernet Communication Module IFD9507