Ethernet Communication Module DVPEN01-SL
DVP-PLC Application Manual
5
2.3 LED
Indicators
Indicator
Color
Indication
POWER Green
Power
indication
RS-232
Red
Communication status of the series port
100M Orange
Network
connection
status
LINK
Green
Network communication speed
2.4 RJ-45 PIN Definition
RJ-45 sketch
Terminal No.
Definition
Explanation
1
Tx+
Positive pole for data transmission
2
Tx-
Negative pole for data transmission
3
Rx+
Positive pole for data receiving
6
Rx-
Negative pole for data receiving
4, 5, 7, 8
-
N/C
3
Installation & Wiring
This section gives instructions on how to connect DVPEN01-SL with PLC MPU and how to connect
DVPEN01-SL to the network.
3.1 Installation
Connect PLC MPU to DVPEN01-SL
z
Adjust the extension clip on the left side of the MPU.
z
Meet the extension port of the MPU with DVPEN01-SL as shown in the figure below.
z
Fasten the extension clip.
DVP28SV
LAN
RS-232
RS-232
LINK
100M
DVPEN01
POWER
Connect DVPEN01-SL to other extension modules
z
To connect DVPEN01-SL with the other extension module, lift the extension clip of the extension
module by a screwdriver and open the side cover.