Ethernet Communication Module DVPEN01-SL
DVP-PLC Application Manual
23
1.
Enable
Data
Exchange:
Check the box to enable or disable data exchange. Start data exchange after enable it.
2. Communication Address & Data exchange host IP:
You have to enter the IP address of DVPEN01-SL at the other end. For example, if you would like
DVPEN01-SL to exchange data with 192.168.0.1, set No. 1 as 192.168.0.1. When the data are
being exchanged, if the value in CR#28 is H’0001, the data will be exchanged with 192.168.0.1.
3. See “Application Examples Section 6.11” for more details.
5.6 IP
Filter
IP filter is used for restricting the connection of the network in case some uncertain IP will cause errors. Only
the IP set within a certain range can establish a connection. Other IPs will be rejected.
Setting up IP filter