- 8 -
- 9 -
EN
1. Presentation
2. Location
Locations to avoid
Do not install the detector:
• Within a metre from vents for heating, cooling or circulating air.
The smoke could be blown away from the detector or be diluted.
• In a place where the temperature could drop beneath 0°C or rise above
+50°C; risk of detector not working correctly.
• In a place where there is a risk of condensation. Bathrooms and laundry
rooms are not recommended.
• Places where smoke could gather (kitchen or poorly ventilated garage) and
cause false alarms.
• In a place that is excessively dusty.
Do not install in non-converted attics.
Additional installation recommendations, as well as the "Mandatory
Performance Declaration" for this equipment are available in the
product fi le for
DFR TYXAL+
on our website www.deltadore.com
Material manufactured by SHD BP10809 under reference DOF79R.
The detector can be associated with a DELTA DORE wireless X3D alarm and
control system.
Functional check and maintenance:
You must check that your detector is functional once a
month or after each battery change.
Pressing the “test” button on the case for a few seconds
will light up the LED and the detector will emit 2 beeps.
Quick fl ashing from the detector means that it has
switched to pre-alarm mode (multiple readings).
If the detector’s sensors confi rms the presence of smoke,
the alarm will be activated.
Do not try to trigger the alarm any other way (using a lighter, etc.) because you
could damage the detector or even start a fi re.
Your detector has been designed to require the minimum maintenance possi-
ble. However, some simple actions need to be performed once a year.
After having removed the detector:
• Clean the cracks in the detector (located on the side) with a vacuum clean-
er, using a soft brush or a vacuum cleaner accessory.
• Use a slightly damp cloth to clean the outside of the case.
• Do not blow on the detector to avoid lifting dust.
4
OK
2
1
3
>3s
It is recommended that the detector be replaced after 10 years.
2. Location
20 cm
90 cm
15-25
cm
60 cm
• The detector should preferentially be at-
tached to the ceiling in the middle of the room.
Otherwise, attach it more than 20cm from any
obstacle (partition wall, beam, etc.) and over
60cm from any room corner.
• If this is impossible, attach the detector to
the wall at a distance of between 15 and 25cm
from the ceiling.
• In the case of an angled ceiling, attach the
detector at a location between 20 and 90 cm
vertically below the highest point.
In the home:
In the room:
Recommended locations:
• For enhanced protection:
- Place a detector in each room, avert using listed places to avoid.
• For basic protection:
- Place a detector on each fl oor.
- Place a detector close to sleeping areas
(for example, in the corridor leading to rooms; in the case
of a long corridor > 10m, place 1 detector at each end).
- Place a detector in each bedroom occupied by a smoker.
Flat
House
Dining
room
Kitchen
Bedroom
Smoker
bedroom
Lounge
Bedroom
Basic protection
Enhanced protection
Bedroom
Bedroom
Lounge
Kitchen
Basement
Corridor