Delta Controls DNS-24 Application Manual Download Page 39

Delta Controls 

Document Edition 4.2

 

 

Page 39 of 43 

An LCD object is automatically created for each BACstat connected to the LINKnet network. 
However, the associated AI objects representing the room temperature in each BACstat must be 
created manually, and must follow a predefined numbering scheme. For DAC products the LINKnet 
object instance number is the LINKnet device address (1 to 12) multiplied by 100, plus the MS/TP 
object instance number. For example, you would create AI501 in the Application Controller to 
represent the 10K Thermistor value on a BACstat with a LINKnet device address of 5. 

For enteliBUS products the LINKnet object instance number is the LINKnet device address (1 to 12) 
multiplied by 200,000, plus the MS/TP object instance number. 

With V3.22 or higher loaded in the Application Controller, AV objects may be created in a similar 
fashion to the AI objects, which map to corresponding AV objects in the BACstat. You can then use 
these in GCL+ programming as well. With V3.21, mapped AV objects are not supported. 

Software & Programming

 

OBJECTS 

The following is a list of predefined objects that reside in the BACstat II which are accessible over a 
LINKnet connection by creating objects in its parent controller as described in the preceding section.  

Object 

Name 

Description 

Default Value 

AIx01 

Temperature 

Input 1 (10K Thermistor Value) 

N/A 

AIx02 

Input 2 * 

Input 2 (Available Input in DNT models) 

N/A 

AIx03 

Humidity 

Input 3 (Humidity H option) 

N/A 

 

Input 3 * 

Input 3 (Extra Input on DNT-T221) 

N/A 

AIx04 

CO2 

Input 4 (CO2 – C option on DNS-x24 models) 

N/A 

BIx05 

Motion 

Input 5 (Motion -  M option on DNS-x24 
models) 

N/A 

BOx01 

Output 1 * 

Output 1 on DNT-T103 

N/A 

BOx02 

Output 2 * 

Output 2 on DNT-T103 

N/A 

BOx03 

Output 3 * 

Output 3 on DNT-T103 

N/A 

AOx01 

Output 1 * 

Output 1 on DNT-T221 

N/A 

AOx02 

Output 2 * 

Output 2 on DNT-T221 

N/A 

BOx03 

Output 3 * 

Output 3 on DNT-T221  

N/A 

AVx04 

 

KeyPress 

KeyPress Value 

N/A 

AVx06 

 

Day Setpoint 

Room Setpoint 

ºC = 21; ºF = 71; % = 30 

AVx07 

 

Day Minimum 

Minimum Adjustable Day Setpoint 

ºC = 18; ºF = 65; % = 20 

AVx08 

 

Day Maximum 

Maximum Adjustable Day Setpoint 

ºC = 25; ºF = 77; % = 55 

AVx09 

 

Day Differential 

Room Setpoint Differential 

ºC = ±0.5; ºF = ±1, % = ±2.5 

AVx10 

 

Night Heat Setpoint 

Night Setpoint for Heating (or Humidity) 

ºC = 16; ºF = 60; % = 30 

AVx11 

 

Night Cool Setpoint

 

Night Setpoint for Cooling 

ºC = 30; ºF = 86; % = 30 

AVx15 

Display Code 

Local Display & Button Handling  

1237 

AVx16 

AI1 Calibration 

Input 1 Calibration (Temperature) 

0.0 

AVx17 

AI2 Calibration 

Input 2 Calibration (MUXed IP) 

0.0 

AVx18 

AI3 Calibration 

Input 3 Calibration (Humidity) 

0.0 

AVx30 

Baud Rate 

Network Baud Rate 

AVx31 

PIN 

PIN (4-Bit Configuration Access Code) 

1011 

*  Names are user settable (to a maximum of 32 characters), and only on outputs when they are controlled remotely (i.e., 

MUXed). 

 

These are the typical objects that may be commanded on the fly by a user or from GCL++, and also include the 

Outputs when they are MUXed.  

Summary of Contents for DNS-24

Page 1: ...work and have termination resistors that are jumper selectable The DNS 24 models are network sensors they have multiple onboard sensor options including temperature humidity CO2 and motion but do not...

Page 2: ...Data exchange may be done in GCL programming in any DCU or Application Controller on the MS TP network Setup Configuration NETWORK COMMUNICATIONS On an MS TP network BACstats communicate at a default...

Page 3: ...he Configuration Menu you do not press a button for 2 minutes the BACstat will exit the Configuration Menu and return to normal display mode 2 BUTTON NAVIGATION FUNCTIONS The Button functions are as f...

Page 4: ...trategy and allows you to configure the outputs for your Radiant Heating application This enables the Humidity control strategy and allows you to configure the outputs for your Humidity application Av...

Page 5: ...tom i e Setpoint Value 1 to 5 1 Disabled 2 No Setpoint until an arrow button is pressed adjustable 3 Setpoint is always displayed adjustable 4 No Setpoint until an arrow button is pressed not adjustab...

Page 6: ...n LINKnet is On Menu Item Description The device Address 1 to 99 which is used internally as the MAC Address As the BACstat can only be a Subnet device on MS TP this address is always mapped in as the...

Page 7: ...or you wish to move on press NEXT or PREVIOUS If at any time you do not press a button for 30 minutes the BACstat will exit Service Tool Mode and return to normal display mode Any outputs commanded m...

Page 8: ...the box to the minimum value Displays the current Maximum Air Flow setting use the arrow keys to navigate the submenus to adjust the value force the box to the maximum value and calibrate the display...

Page 9: ...n sensor Only available on DNS 24 models Unless inputs are multiplexed many of the input units and associated scale ranges are automatically set when a built in application is selected Also refer to p...

Page 10: ...required AV27 Setup 4 Setup Variable 4 Name Changes As required AV28 Setup 5 Setup Variable 5 Name Changes As required AV29 Setup 6 Setup Variable 6 Name Changes As required AV30 Baud Rate Network Bau...

Page 11: ...on board motion sensor option M the motion sensor shows up as binary input 5 The motion option is only available on the DNS M24 and DNS CHM24 The Motion sensor has a configurable latch time set in se...

Page 12: ...ication S Service or O Other which is followed by a two digit code For example 02 05 06 10 12 47 S04 The PresentValue indicates how many items are in the log Code Description H01 EEPROM communication...

Page 13: ...and setpoint changes based on Time of Day or other conditions WITH V3 21 FIRMWARE All GCL programming for mode changes DCU DSC or DAC data exchange and other strategies must be written in the DCU WITH...

Page 14: ...l and associated icons are completely disabled as though no heating stages even exist 20 Cooling Lockout All cooling control and associated icons are completely disabled as though no cooling stages ev...

Page 15: ...3 can be set to either cooling default or heating When set to cooling the air supply is treated as the first stage of cooling When set to heating the cooling controller is inverted and the air supply...

Page 16: ...tpoint OCCUPIED Uses Day Setpoint AV6 UNOCCUPIED Uses Night Heat Setpoint AV10 if the Input is below the Night Heat Setpoint AV6 and uses the Night Cool Setpoint AV11 if the Input is above the Night C...

Page 17: ...ng and Cooling will not be ON at the same time If the Input temperature is less than Day Setpoint Day Differential Deadband then the controller is in HEATING If the Input temperature is greater than D...

Page 18: ...doing provides the first stage of heating Any additional stages of heating modulate open over 100 to 200 Therefore only when the Box Mode is in heating does the Controller Status AV14 modulate to a va...

Page 19: ...he fly What follows hereafter is a working description for each of these setpoints If the particular setpoint is settable in the Configuration Menu it is indicated with its LCD text Day Setpoint AV6 T...

Page 20: ...setpoint used internally for cooling control which is the Day Setpoint Day Differential This value is not directly adjustable It can only be adjusted by setting either the Day Setpoint or the Day Diff...

Page 21: ...M Dir or Rev Analog Dir or Rev Analog VAV FlowDamper Tri State Actuator Tri State VAV FlowDamper Heating Stage 1 H1 Heating Stage 2 H2 Heating Stage 3 H3 Cooling Stage 1 C1 Cooling Stage 2 C2 Cooling...

Page 22: ...Air Flow 0 to 1 N A Optional OAT Tri State Flow Damper Open Tri State Flow Damper Close Heating 1 Room Temp Air Flow 0 to 1 N A Optional OAT Tri State Flow Damper Open Tri State Flow Damper Close Fan...

Page 23: ...1 the analog damper output 1 is used to control airflow but also requires that an appropriate runtime be set for the actuator via Setup variable AV24 In Unoccupied Deadband mode the Airflow Setpoint i...

Page 24: ...3 Room Temp N A Optional OAT Analog Damper Cooling 1 Heating 1 Heating 2 Room Temp N A Optional OAT Analog Damper Cooling 1 Heating 1 Fan Room Temp N A Optional OAT Analog Damper Cooling 1 Heating 1 N...

Page 25: ...is used to control damper position but also requires a runtime value set in AV24 In Unoccupied Deadband mode the damper position is set to zero Output 3 may be selected as a fan which would operate ac...

Page 26: ...ersing Valve 0 10v None MUX Setup Parameters Setup Variable Function Notes AV24 Binary Delay Transition Timer for Compressor AV25 N A AV26 Binary Delay Transition Timer for Rev Valve AV27 N A AV28 PWM...

Page 27: ...3 Binary Delay NOTE The analog outputs on the DNT T221 do not modulate but provide a 0 or 10v signal for the compressor and reversing valve and require interface relays for switching purposes 5 FAN CO...

Page 28: ...r heating and cooling both become less than 1 a delay counter for stopping the fan will be started Once the delay time has expired Setpoint 28 Output 3 Binary Delay the fan output will be turned off 6...

Page 29: ...Input AI3 Remote AV5 Output 1 Output 2 Output 3 Room Temp Optional Room Humidity Optional OAT Humidifier MUX MUX DNT H121 I O Outputs 1 2 are Analog and Output 3 is a Triac Input AI1 Input AI2 Input...

Page 30: ...ut is connected to a constant fan 80 The associated output is connected to a manually controlled fan 90 Compressor The associated output is connected to a HPU compressor 100 Reversing Valve The associ...

Page 31: ...s the type so 10 0 4 10 4 1 BINARY OUTPUTS If the binary output is selected as MUX it simply transfers the value written to the corresponding variable AV1 AV2 or AV3 to the physical output There is no...

Page 32: ...puts 2 and 3 while the DNT T221 can have one stage Output 3 These are similar to the PWM outputs except The cycle time is fixed at ten seconds At a controller value of 0 the outputs are always OFF At...

Page 33: ...ng valve is to be used cross connect the Open and Close outputs 5 FAN CONTROL There are three modes of operation Fan Type Occupied Mode Unoccupied Mode Continuous Fan ON constantly ON when the Control...

Page 34: ...ciated runtime setting If the application is something other than VAV or VVT then both analog outputs may be configured for either heating or cooling Analog outputs for heating or cooling may be eithe...

Page 35: ...to enable or disable access AI2 AND AI3 CONFIGURATION While AI1 is typically configured from the Configuration Menu by setting the Temperature Units setting degrees C or F additional inputs such as A...

Page 36: ...ack on again Reload DESCRIPTORS This will reload the BACstat descriptors up into ORCAview OWS This is particularly useful if for some reason the OWS is out of sync with what objects and object names t...

Page 37: ...limit the frequency of such commands Otherwise you will create excessive network traffic 3 COMMAND PRIORITY Both GCL programs and user commands i e manual mode have the same write priority for all ob...

Page 38: ...in the BACstat Calibrate the BACstats locally via Service Tool Menu or use the mapped AV objects See the Objects table Do not calibrate the AI objects in the Application Controller Device Limitations...

Page 39: ...ure Input 1 10K Thermistor Value N A AIx02 Input 2 Input 2 Available Input in DNT models N A AIx03 Humidity Input 3 Humidity H option N A Input 3 Input 3 Extra Input on DNT T221 N A AIx04 CO2 Input 4...

Page 40: ...splay and button handling i e AVx15 1111 and program everything in GCL in the Application Controller as previously described for V3 21 firmware Or by setting the Display Code to something other than 1...

Page 41: ...alibrate text is turned on On 0 On text is turned off 1 On text is turned on Off 0 Off text is turned off 1 Off text is turned on Time 0 Time text is turned off 1 Time text is turned on Minimum 0 Min...

Page 42: ...es as often as you require but it is still recommended practice to use DOEVERY statements And of course you may read any object value as often as you can there is no issue with reading GCL PROGRAMMING...

Page 43: ...ents the first hundreds digit of a 3 digit number Note that processing KeyPress values is disabled when using the Configuration or Service Tool menu Here is the list of KeyPress values If the display...

Reviews: