Delta Controls DNS-24 Application Manual Download Page 2

DNS-24, DNT-T103 & DNT-T221 Application Guide

 

Page 2 of 43

 

 

Document Edition 4.2

 

Other Relevant Documents 

 

Associated BACstat II Installation Guide (DNS-x24, DNT-T103 or DNT-221) 

 

Delta Controls Wiring and Installation Guidelines 

 

ORCAview Operator Guide 

 

ORCAview Technical Reference Manual

 

 

Release Notes for relevant firmware and BACstat products 

Important Information 

This document has been updated to include features and capabilities of Release 4a firmware and 
hardware for the BACstat II DNS-x24, DNT-T103 and the DNT-T221 products. Although BACstat 
firmware is independent from ORCAview, DCU, and Application Controllers, certain BACstat 
capabilities require support in the other products. The firmware for hardware revision 4 (or greater) 
DNS-24, DNT-T103 and the DNT-T221 can be flash loaded over the network. 

1.

 

V3.22

 

F

IRMWARE 

&

 

S

OFTWARE OR 

H

IGHER

 

When BACstats are used with ORCAview, DCU, and Application Controllers loaded with V3.22 
firmware/software please be aware of the following issues. 

For an MS/TP Network Connection: 

 

A DSC is required 

 

Local BACstat display handling and control strategies may be enabled 

 

Data exchange may be done in GCL+ programming in any DCU or Application Controller 
on the MS/TP network

 

Setup & Configuration 

NETWORK COMMUNICATIONS 

On an MS/TP network BACstats communicate at a default speed of 76,800 bps. Refer to the 

Technical Reference Manual

 for further detail on configuring the MS/TP network or changing 

baud rates. Also refer to the associated 

BACstat II Installation Guide

 for network installation 

details. 

Flash Programming  

 The BACstat II Release 4 product now offers flash loadable firmware across its network 
connection. It is supported by Flashloader V3.33, and operates the same way as other Delta 
controllers. Please ensure that all the databases have been backed up prior to upgrading the flash 
firmware. Refer to the 

Flashloader V3.33 User's Guide 

for further details on using the 

Flashloader to upgrade the firmware on the BACstat II Release 4 product. 

DEVICE CONFIGURATION (KEYPAD) 

To use ORCAview OWS to configure BACstats refer t

OWS Functions

 on page 34. 

1.

 

C

ONFIGURATION 

M

ENU 

U

SER 

A

CCESS

 

Access to the Configuration Menu is protected by an access code or PIN. You must enter the valid PIN 
before access is granted, which works as follows: 

 

First press the Up Arrow (▲), and then press the Down Arrow (▼) while still pressing the Up 
Arrow, and hold them both down for at least 5 seconds. 

Summary of Contents for DNS-24

Page 1: ...work and have termination resistors that are jumper selectable The DNS 24 models are network sensors they have multiple onboard sensor options including temperature humidity CO2 and motion but do not...

Page 2: ...Data exchange may be done in GCL programming in any DCU or Application Controller on the MS TP network Setup Configuration NETWORK COMMUNICATIONS On an MS TP network BACstats communicate at a default...

Page 3: ...he Configuration Menu you do not press a button for 2 minutes the BACstat will exit the Configuration Menu and return to normal display mode 2 BUTTON NAVIGATION FUNCTIONS The Button functions are as f...

Page 4: ...trategy and allows you to configure the outputs for your Radiant Heating application This enables the Humidity control strategy and allows you to configure the outputs for your Humidity application Av...

Page 5: ...tom i e Setpoint Value 1 to 5 1 Disabled 2 No Setpoint until an arrow button is pressed adjustable 3 Setpoint is always displayed adjustable 4 No Setpoint until an arrow button is pressed not adjustab...

Page 6: ...n LINKnet is On Menu Item Description The device Address 1 to 99 which is used internally as the MAC Address As the BACstat can only be a Subnet device on MS TP this address is always mapped in as the...

Page 7: ...or you wish to move on press NEXT or PREVIOUS If at any time you do not press a button for 30 minutes the BACstat will exit Service Tool Mode and return to normal display mode Any outputs commanded m...

Page 8: ...the box to the minimum value Displays the current Maximum Air Flow setting use the arrow keys to navigate the submenus to adjust the value force the box to the maximum value and calibrate the display...

Page 9: ...n sensor Only available on DNS 24 models Unless inputs are multiplexed many of the input units and associated scale ranges are automatically set when a built in application is selected Also refer to p...

Page 10: ...required AV27 Setup 4 Setup Variable 4 Name Changes As required AV28 Setup 5 Setup Variable 5 Name Changes As required AV29 Setup 6 Setup Variable 6 Name Changes As required AV30 Baud Rate Network Bau...

Page 11: ...on board motion sensor option M the motion sensor shows up as binary input 5 The motion option is only available on the DNS M24 and DNS CHM24 The Motion sensor has a configurable latch time set in se...

Page 12: ...ication S Service or O Other which is followed by a two digit code For example 02 05 06 10 12 47 S04 The PresentValue indicates how many items are in the log Code Description H01 EEPROM communication...

Page 13: ...and setpoint changes based on Time of Day or other conditions WITH V3 21 FIRMWARE All GCL programming for mode changes DCU DSC or DAC data exchange and other strategies must be written in the DCU WITH...

Page 14: ...l and associated icons are completely disabled as though no heating stages even exist 20 Cooling Lockout All cooling control and associated icons are completely disabled as though no cooling stages ev...

Page 15: ...3 can be set to either cooling default or heating When set to cooling the air supply is treated as the first stage of cooling When set to heating the cooling controller is inverted and the air supply...

Page 16: ...tpoint OCCUPIED Uses Day Setpoint AV6 UNOCCUPIED Uses Night Heat Setpoint AV10 if the Input is below the Night Heat Setpoint AV6 and uses the Night Cool Setpoint AV11 if the Input is above the Night C...

Page 17: ...ng and Cooling will not be ON at the same time If the Input temperature is less than Day Setpoint Day Differential Deadband then the controller is in HEATING If the Input temperature is greater than D...

Page 18: ...doing provides the first stage of heating Any additional stages of heating modulate open over 100 to 200 Therefore only when the Box Mode is in heating does the Controller Status AV14 modulate to a va...

Page 19: ...he fly What follows hereafter is a working description for each of these setpoints If the particular setpoint is settable in the Configuration Menu it is indicated with its LCD text Day Setpoint AV6 T...

Page 20: ...setpoint used internally for cooling control which is the Day Setpoint Day Differential This value is not directly adjustable It can only be adjusted by setting either the Day Setpoint or the Day Diff...

Page 21: ...M Dir or Rev Analog Dir or Rev Analog VAV FlowDamper Tri State Actuator Tri State VAV FlowDamper Heating Stage 1 H1 Heating Stage 2 H2 Heating Stage 3 H3 Cooling Stage 1 C1 Cooling Stage 2 C2 Cooling...

Page 22: ...Air Flow 0 to 1 N A Optional OAT Tri State Flow Damper Open Tri State Flow Damper Close Heating 1 Room Temp Air Flow 0 to 1 N A Optional OAT Tri State Flow Damper Open Tri State Flow Damper Close Fan...

Page 23: ...1 the analog damper output 1 is used to control airflow but also requires that an appropriate runtime be set for the actuator via Setup variable AV24 In Unoccupied Deadband mode the Airflow Setpoint i...

Page 24: ...3 Room Temp N A Optional OAT Analog Damper Cooling 1 Heating 1 Heating 2 Room Temp N A Optional OAT Analog Damper Cooling 1 Heating 1 Fan Room Temp N A Optional OAT Analog Damper Cooling 1 Heating 1 N...

Page 25: ...is used to control damper position but also requires a runtime value set in AV24 In Unoccupied Deadband mode the damper position is set to zero Output 3 may be selected as a fan which would operate ac...

Page 26: ...ersing Valve 0 10v None MUX Setup Parameters Setup Variable Function Notes AV24 Binary Delay Transition Timer for Compressor AV25 N A AV26 Binary Delay Transition Timer for Rev Valve AV27 N A AV28 PWM...

Page 27: ...3 Binary Delay NOTE The analog outputs on the DNT T221 do not modulate but provide a 0 or 10v signal for the compressor and reversing valve and require interface relays for switching purposes 5 FAN CO...

Page 28: ...r heating and cooling both become less than 1 a delay counter for stopping the fan will be started Once the delay time has expired Setpoint 28 Output 3 Binary Delay the fan output will be turned off 6...

Page 29: ...Input AI3 Remote AV5 Output 1 Output 2 Output 3 Room Temp Optional Room Humidity Optional OAT Humidifier MUX MUX DNT H121 I O Outputs 1 2 are Analog and Output 3 is a Triac Input AI1 Input AI2 Input...

Page 30: ...ut is connected to a constant fan 80 The associated output is connected to a manually controlled fan 90 Compressor The associated output is connected to a HPU compressor 100 Reversing Valve The associ...

Page 31: ...s the type so 10 0 4 10 4 1 BINARY OUTPUTS If the binary output is selected as MUX it simply transfers the value written to the corresponding variable AV1 AV2 or AV3 to the physical output There is no...

Page 32: ...puts 2 and 3 while the DNT T221 can have one stage Output 3 These are similar to the PWM outputs except The cycle time is fixed at ten seconds At a controller value of 0 the outputs are always OFF At...

Page 33: ...ng valve is to be used cross connect the Open and Close outputs 5 FAN CONTROL There are three modes of operation Fan Type Occupied Mode Unoccupied Mode Continuous Fan ON constantly ON when the Control...

Page 34: ...ciated runtime setting If the application is something other than VAV or VVT then both analog outputs may be configured for either heating or cooling Analog outputs for heating or cooling may be eithe...

Page 35: ...to enable or disable access AI2 AND AI3 CONFIGURATION While AI1 is typically configured from the Configuration Menu by setting the Temperature Units setting degrees C or F additional inputs such as A...

Page 36: ...ack on again Reload DESCRIPTORS This will reload the BACstat descriptors up into ORCAview OWS This is particularly useful if for some reason the OWS is out of sync with what objects and object names t...

Page 37: ...limit the frequency of such commands Otherwise you will create excessive network traffic 3 COMMAND PRIORITY Both GCL programs and user commands i e manual mode have the same write priority for all ob...

Page 38: ...in the BACstat Calibrate the BACstats locally via Service Tool Menu or use the mapped AV objects See the Objects table Do not calibrate the AI objects in the Application Controller Device Limitations...

Page 39: ...ure Input 1 10K Thermistor Value N A AIx02 Input 2 Input 2 Available Input in DNT models N A AIx03 Humidity Input 3 Humidity H option N A Input 3 Input 3 Extra Input on DNT T221 N A AIx04 CO2 Input 4...

Page 40: ...splay and button handling i e AVx15 1111 and program everything in GCL in the Application Controller as previously described for V3 21 firmware Or by setting the Display Code to something other than 1...

Page 41: ...alibrate text is turned on On 0 On text is turned off 1 On text is turned on Off 0 Off text is turned off 1 Off text is turned on Time 0 Time text is turned off 1 Time text is turned on Minimum 0 Min...

Page 42: ...es as often as you require but it is still recommended practice to use DOEVERY statements And of course you may read any object value as often as you can there is no issue with reading GCL PROGRAMMING...

Page 43: ...ents the first hundreds digit of a 3 digit number Note that processing KeyPress values is disabled when using the Configuration or Service Tool menu Here is the list of KeyPress values If the display...

Reviews: