4.

 

R

ESET 

A

CTION 

(R

ESET 

R

ATE IN REPEA TS PER HOUR

If the Reset Rate is non-zero, reset action is enabled. As long as there is a difference (or error) between 
the input value (i.e., space temperature) and setpoint value, reset action will increment or decrement the 

Controller Status

 value (AV14) over time - in proportion to the value of the reset rate and the magnitude 

of the error - in an attempt to remove the error. In this way, the 

Controller Status

 value is continually 

fluctuating in order to reach setpoint.  

The amount of reset does not decrease internally as the input value approaches setpoint, but the reset 
value is frozen while in deadband. The only time reset action has no affect on the controller output is 
when the input is equal to the setpoint (no error). For this reason, be cautious about applying too much 
reset action, otherwise you may cause unnecessary movement on actuators. By setting Reset Rate to 0, 
you disable reset action altogether. 

SETPOINTS 

The BACstat II uses a series of setpoints for various purposes, most of which interact with one 
another. For a complete list of these setpoints and other objects and their defaults, refer to the 
Object table on page 9. When you change the units setting between ºC and ºF all of these 
setpoints revert back to their matching default values – the BACstat does not do a conversion on 
the fly. What follows hereafter is a working description for each of these setpoints. If the 
particular setpoint is settable in the Configuration Menu it is indicated with its LCD text.

 

Day Setpoint (AV6) – 



 

This is the setpoint used when in D

AY

 mode. With the 

Display Code

 (AV15) set to an appropriate 

value the setpoint can be adjusted up or down by pressing the buttons. Whether or not this 
setpoint is displayed or is adjustable on the LCD, it is used internally for control. The units for the 
setpoint are ºC or ºF (as per AI1) unless the second digit of the 

Display Code

 (AV15) is set to 3 

(for Humidity), in which case the units become %RH. The value for Day Setpoint can also be set 
in the Configuration Menu, or by commanding the variable (via GCL+ or ORCAview OWS or 3

rd

 

Party devices). 

Day Minimum Setpoint (AV7) – 



 

This is the minimum value a user can adjust the 

Day Setpoint

 to. If an attempt is made to adjust 

the 

Day Setpoint

 lower, it will not change. If a lower value is commanded from the OWS or 

another device, it will not accept the change. The value for Day Minimum Setpoint can be set in 
the Configuration Menu, or by commanding the variable (via GCL+ or ORCAview OWS or 3

rd

 

Party devices). 

Day Maximum Setpoint (AV8) – 



 

This is the maximum value a user can adjust the 

Day Setpoint

 to. If an attempt is made to adjust 

the 

Day Setpoint 

higher it will not change. If a higher value is commanded from the OWS or 

another device, it will not accept the change. The value for Day Maximum Setpoint can be set in 
the Configuration Menu, or by commanding the variable (via GCL+ or ORCAview OWS or 3

rd

 

Party devices). 

Summary of Contents for DNS-24

Page 1: ...work and have termination resistors that are jumper selectable The DNS 24 models are network sensors they have multiple onboard sensor options including temperature humidity CO2 and motion but do not...

Page 2: ...Data exchange may be done in GCL programming in any DCU or Application Controller on the MS TP network Setup Configuration NETWORK COMMUNICATIONS On an MS TP network BACstats communicate at a default...

Page 3: ...he Configuration Menu you do not press a button for 2 minutes the BACstat will exit the Configuration Menu and return to normal display mode 2 BUTTON NAVIGATION FUNCTIONS The Button functions are as f...

Page 4: ...trategy and allows you to configure the outputs for your Radiant Heating application This enables the Humidity control strategy and allows you to configure the outputs for your Humidity application Av...

Page 5: ...tom i e Setpoint Value 1 to 5 1 Disabled 2 No Setpoint until an arrow button is pressed adjustable 3 Setpoint is always displayed adjustable 4 No Setpoint until an arrow button is pressed not adjustab...

Page 6: ...n LINKnet is On Menu Item Description The device Address 1 to 99 which is used internally as the MAC Address As the BACstat can only be a Subnet device on MS TP this address is always mapped in as the...

Page 7: ...or you wish to move on press NEXT or PREVIOUS If at any time you do not press a button for 30 minutes the BACstat will exit Service Tool Mode and return to normal display mode Any outputs commanded m...

Page 8: ...the box to the minimum value Displays the current Maximum Air Flow setting use the arrow keys to navigate the submenus to adjust the value force the box to the maximum value and calibrate the display...

Page 9: ...n sensor Only available on DNS 24 models Unless inputs are multiplexed many of the input units and associated scale ranges are automatically set when a built in application is selected Also refer to p...

Page 10: ...required AV27 Setup 4 Setup Variable 4 Name Changes As required AV28 Setup 5 Setup Variable 5 Name Changes As required AV29 Setup 6 Setup Variable 6 Name Changes As required AV30 Baud Rate Network Bau...

Page 11: ...on board motion sensor option M the motion sensor shows up as binary input 5 The motion option is only available on the DNS M24 and DNS CHM24 The Motion sensor has a configurable latch time set in se...

Page 12: ...ication S Service or O Other which is followed by a two digit code For example 02 05 06 10 12 47 S04 The PresentValue indicates how many items are in the log Code Description H01 EEPROM communication...

Page 13: ...and setpoint changes based on Time of Day or other conditions WITH V3 21 FIRMWARE All GCL programming for mode changes DCU DSC or DAC data exchange and other strategies must be written in the DCU WITH...

Page 14: ...l and associated icons are completely disabled as though no heating stages even exist 20 Cooling Lockout All cooling control and associated icons are completely disabled as though no cooling stages ev...

Page 15: ...3 can be set to either cooling default or heating When set to cooling the air supply is treated as the first stage of cooling When set to heating the cooling controller is inverted and the air supply...

Page 16: ...tpoint OCCUPIED Uses Day Setpoint AV6 UNOCCUPIED Uses Night Heat Setpoint AV10 if the Input is below the Night Heat Setpoint AV6 and uses the Night Cool Setpoint AV11 if the Input is above the Night C...

Page 17: ...ng and Cooling will not be ON at the same time If the Input temperature is less than Day Setpoint Day Differential Deadband then the controller is in HEATING If the Input temperature is greater than D...

Page 18: ...doing provides the first stage of heating Any additional stages of heating modulate open over 100 to 200 Therefore only when the Box Mode is in heating does the Controller Status AV14 modulate to a va...

Page 19: ...he fly What follows hereafter is a working description for each of these setpoints If the particular setpoint is settable in the Configuration Menu it is indicated with its LCD text Day Setpoint AV6 T...

Page 20: ...setpoint used internally for cooling control which is the Day Setpoint Day Differential This value is not directly adjustable It can only be adjusted by setting either the Day Setpoint or the Day Diff...

Page 21: ...M Dir or Rev Analog Dir or Rev Analog VAV FlowDamper Tri State Actuator Tri State VAV FlowDamper Heating Stage 1 H1 Heating Stage 2 H2 Heating Stage 3 H3 Cooling Stage 1 C1 Cooling Stage 2 C2 Cooling...

Page 22: ...Air Flow 0 to 1 N A Optional OAT Tri State Flow Damper Open Tri State Flow Damper Close Heating 1 Room Temp Air Flow 0 to 1 N A Optional OAT Tri State Flow Damper Open Tri State Flow Damper Close Fan...

Page 23: ...1 the analog damper output 1 is used to control airflow but also requires that an appropriate runtime be set for the actuator via Setup variable AV24 In Unoccupied Deadband mode the Airflow Setpoint i...

Page 24: ...3 Room Temp N A Optional OAT Analog Damper Cooling 1 Heating 1 Heating 2 Room Temp N A Optional OAT Analog Damper Cooling 1 Heating 1 Fan Room Temp N A Optional OAT Analog Damper Cooling 1 Heating 1 N...

Page 25: ...is used to control damper position but also requires a runtime value set in AV24 In Unoccupied Deadband mode the damper position is set to zero Output 3 may be selected as a fan which would operate ac...

Page 26: ...ersing Valve 0 10v None MUX Setup Parameters Setup Variable Function Notes AV24 Binary Delay Transition Timer for Compressor AV25 N A AV26 Binary Delay Transition Timer for Rev Valve AV27 N A AV28 PWM...

Page 27: ...3 Binary Delay NOTE The analog outputs on the DNT T221 do not modulate but provide a 0 or 10v signal for the compressor and reversing valve and require interface relays for switching purposes 5 FAN CO...

Page 28: ...r heating and cooling both become less than 1 a delay counter for stopping the fan will be started Once the delay time has expired Setpoint 28 Output 3 Binary Delay the fan output will be turned off 6...

Page 29: ...Input AI3 Remote AV5 Output 1 Output 2 Output 3 Room Temp Optional Room Humidity Optional OAT Humidifier MUX MUX DNT H121 I O Outputs 1 2 are Analog and Output 3 is a Triac Input AI1 Input AI2 Input...

Page 30: ...ut is connected to a constant fan 80 The associated output is connected to a manually controlled fan 90 Compressor The associated output is connected to a HPU compressor 100 Reversing Valve The associ...

Page 31: ...s the type so 10 0 4 10 4 1 BINARY OUTPUTS If the binary output is selected as MUX it simply transfers the value written to the corresponding variable AV1 AV2 or AV3 to the physical output There is no...

Page 32: ...puts 2 and 3 while the DNT T221 can have one stage Output 3 These are similar to the PWM outputs except The cycle time is fixed at ten seconds At a controller value of 0 the outputs are always OFF At...

Page 33: ...ng valve is to be used cross connect the Open and Close outputs 5 FAN CONTROL There are three modes of operation Fan Type Occupied Mode Unoccupied Mode Continuous Fan ON constantly ON when the Control...

Page 34: ...ciated runtime setting If the application is something other than VAV or VVT then both analog outputs may be configured for either heating or cooling Analog outputs for heating or cooling may be eithe...

Page 35: ...to enable or disable access AI2 AND AI3 CONFIGURATION While AI1 is typically configured from the Configuration Menu by setting the Temperature Units setting degrees C or F additional inputs such as A...

Page 36: ...ack on again Reload DESCRIPTORS This will reload the BACstat descriptors up into ORCAview OWS This is particularly useful if for some reason the OWS is out of sync with what objects and object names t...

Page 37: ...limit the frequency of such commands Otherwise you will create excessive network traffic 3 COMMAND PRIORITY Both GCL programs and user commands i e manual mode have the same write priority for all ob...

Page 38: ...in the BACstat Calibrate the BACstats locally via Service Tool Menu or use the mapped AV objects See the Objects table Do not calibrate the AI objects in the Application Controller Device Limitations...

Page 39: ...ure Input 1 10K Thermistor Value N A AIx02 Input 2 Input 2 Available Input in DNT models N A AIx03 Humidity Input 3 Humidity H option N A Input 3 Input 3 Extra Input on DNT T221 N A AIx04 CO2 Input 4...

Page 40: ...splay and button handling i e AVx15 1111 and program everything in GCL in the Application Controller as previously described for V3 21 firmware Or by setting the Display Code to something other than 1...

Page 41: ...alibrate text is turned on On 0 On text is turned off 1 On text is turned on Off 0 Off text is turned off 1 Off text is turned on Time 0 Time text is turned off 1 Time text is turned on Minimum 0 Min...

Page 42: ...es as often as you require but it is still recommended practice to use DOEVERY statements And of course you may read any object value as often as you can there is no issue with reading GCL PROGRAMMING...

Page 43: ...ents the first hundreds digit of a 3 digit number Note that processing KeyPress values is disabled when using the Configuration or Service Tool menu Here is the list of KeyPress values If the display...

Reviews: