Table 6. Environmental parameters

Parameter

Specifications

Operating temperature

0°C to 45°C (32°F to 113°F) continuously
-5°C to 45°C (23°F to 113°F) short term

Short term is </= 1% of operational hours per year.

NOTE: 

Reduce maximum temperature by 1°C/300 meters 

(1°F/547 feet) above 950 meters (3,117 feet).

Operating humidity

5% to 85% (RH), non-condensing, continuously
5% to 90% (RH), non-condensing, short term

Short term is </= 1% of operational hours per year.

Storage temperature

–40° to 70°C (–40° to 158°F )

Storage humidity

5% to 95%, non-condensing

Maximum thermal output

600 W = 2047 BTU/Hr

Maximum operational altitude

10,000 feet (3,048 meters)

Maximum non-operational altitude

39,370 feet (12,000 meters)

Shock

Dell EMC Spec SV0115

Table 7. AC power requirements

Parameter

Specifications

Power supply

100–240 VAC 50/60 Hz

Maximum current draw per system

6A/5A at 100/120V AC 3A/2.5A at 200/240V AC

Maximum power consumption

600 Watts

Typical power consumption

300 Watts

Table 8. DC power requirements

Parameter

Specifications

Minimum and maximum input voltage range

−40.5, –60V DC, 15A Max

Maximum power consumption

600 Watts

Start up VDC

39.0 ± 1.5 V

Start off VDC

37.5 ± 1.5 v

IEEE standards

The S4200-ON Series (S4248FB-ON and S4248FBL-ON) switch complies with the following IEEE standards:

802.1ab (LLDP)

802.1ax (Layer 2)

802.1d, 802.1w, 802.1s, 802.1x (Mgmt/Security), 802.3x (Layer 2)

802.3 (1000BASE-KX)

42

Specifications

Summary of Contents for S4248FB-ON

Page 1: ...S4200 ON Series Installation Guide December 2017 ...

Page 2: ...e to hardware or loss of data and tells you how to avoid the problem WARNING A WARNING indicates a potential for property damage personal injury or death Copyright 2017 Dell Inc or its subsidiaries All rights reserved Dell EMC and other trademarks are trademarks of Dell Inc or its subsidiaries Other trademarks may be trademarks of their respective owners 2017 12 Rev A00 ...

Page 3: ...airflow 14 Fan combinations 14 Power 14 Component storage 15 4 NEBS compliance 16 Important information 16 NEBS compliant ground installation 16 5 S4200 ON Series installation 19 Unpack the switch 19 Unpack 19 Rack or cabinet installation 20 Rack mount safety considerations 20 ReadyRails Installation 20 Tool less non threaded mount installation 21 Two post flush mount installation 22 Two post cent...

Page 4: ...fore you install an OS 38 Example of the Grub Bootloader 39 Example of ONIE 39 ONIE service discovery 39 9 Specifications 41 Chassis physical design 41 IEEE standards 42 Agency compliance 43 USA Federal Communications Commission statement 43 European Union EMC directive conformance statement 43 Japan VCCI compliance for class A equipment 44 Korean certification of compliance 44 Electromagnetic com...

Page 5: ... When no cable is connected visible and invisible laser radiation may be emitted from the aperture of the optical transceiver ports Avoid exposure to laser radiation and do not stare into open apertures Regulatory Marketing model S4248FB ON is represented by the regulatory model E22W and the regulatory Type E22W001 Marketing model S4248FBL ON is represented by the regulatory model E22W and the reg...

Page 6: ...AUTION The Caution icon signals information about situations that could result in equipment damage or loss of data WARNING The Warning icon signals information about hardware handling that could result in injury WARNING The ESD Warning icon requires that you take electrostatic precautions when handling the device 6 About this guide ...

Page 7: ...us SFP optics six quad form factor pluggable 28 QSFP28 optics 100GbE 4x25GbE 40GbE and 4x10GbE and two QSFP optics for 40 100GbE aggregation and 1 10GbE top of rack ToR and end of row EoR applications The S4200 ON Series supports the following configurations 48 x 10GbE 6 x 100GbE 40 x 10GbE 8 x 40GbE 48 x 10GbE 12 x 50GbE 48 x 10GbE 24 x 25GbE 72 x 10GbE 40 x 10GbE 2 x 40GbE 6 x 100GbE Figure 2 S4...

Page 8: ...em with 32GB DDR III RAM 64GB iSLC mSATA SSD Non TCAM on board Rangeley CPU system with 8GB DDR III RAM 16GB iSLC mSATA SSD Two hot swappable redundant power supplies Five hot swappable fans modules Standard 1U switch Physical dimensions The S4200 ON Series S4248FB ON and S4248FBL ON has the following physical dimensions 434 x 462 x 44 mm W x D x H 17 1 x 18 2 x 1 72 inches W x D x H PSU and fan m...

Page 9: ...scription System Status Health LED Solid green Normal Operation Blinking green Booting Solid yellow Critical system error Blinking yellow Noncritical system error fan failure or power supply failure Power LED Off No power Solid green Normal Solid yellow POST is in process Blinking yellow Power supply failed FAN LED Solid green Fan powered and running at the expected RPM Blinking yellow Fan failed ...

Page 10: ...G Solid yellow Link operating at a lower speed 1G Flashing yellow 1 second on off Port beacon Activity LED Off No Link Flashing green Port activity NOTE There are four LEDs for each QSFP and QSFP28 port For each port 100GbE or 40GbE uses only one LED 2x50GbE uses two LEDs and 4x25GbE or 4x10GbE uses all four LEDs Table 4 QSFP and QSFP28 port LEDs LED Description Link Activity LED Off No Link Flash...

Page 11: ...h in several different configurations S4248FB ON or S4248FBL ON AC normal airflow Forty 1 10GbE SFP ports two 40GbE or 4x1 10GbE QSFP and six 100 40GbE or 4x25 10GbE or 2x50GbE QSFP28 ports two AC power supplies and five fan subsystems with airflow from the I O side to the power supply side S4248FB ON or S4248FBL ON AC reverse airflow Forty 1 10GbE SFP ports two 40GbE or 4x1 10GbE QSFP and six 100...

Page 12: ...Figure 5 S4200 ON Series luggage tag 1 SVC Tag 2 MAC Address 3 PPID 4 Express Service Code 12 S4200 ON series switch ...

Page 13: ...he following safety requirements Near an adequate power source Connect the switch to the appropriate branch circuit protection according to your local electrical codes Switch environmental temperature range is from 0 to 45 C 32 to 113 F Relative humidity is from 5 to 90 percent noncondensing In a dry clean well ventilated and temperature controlled room away from heat sources such as hot air vents...

Page 14: ...ch Do not mix reverse and normal airflows in a single S4200 ON Series switch For proper ventilation position the switch in an equipment rack or cabinet with a minimum of 5 inches 12 7 cm of clearance around the exhaust vents When you install two S4200 ON Series switches near each other to permit proper airflow position the two switches at least 5 inches 12 7 cm apart The fan speed varies based on ...

Page 15: ...e is from 40 C to 70 C 40 F to 158 F Store on a dry surface or floor away from direct sunlight heat and air conditioning ducts Store in a dust free environment NOTE ESD damage can occur when components are mishandled Always wear an ESD preventive wrist or heel ground strap when handling the S4200 ON Series switch and its accessories After you remove the original packaging place the S4200 ON Series...

Page 16: ...stricted access area were only trained personnel are allowed access Install and connect your switch to the common bonding network CBN You can also install and connect your switch to the central office Connect the battery returns of your switch as DC I Ground your switch using a copper ground conductor Clean and coat all bare grounding connection points on your switch with an antioxidant solution b...

Page 17: ...e shipping bag 3 Clean the bracket and lug surfaces thoroughly and apply an anti oxidant solution to the mating surfaces 4 Attach the switch ground using the Ground cable instructions 5 Using the two removed screws attach the GND lug bracket assembly to your switch as shown Torque the M3 screws to 4 5 in lbs Figure 7 Attach the GND lug assembly NEBS compliance 17 ...

Page 18: ...Figure 8 GND lug assembly attached 6 Install your switch into your rack using the Switch installation instructions 18 NEBS compliance ...

Page 19: ...nd cable Optics installation Switch power up After switch installation Switch replacement Unpack the switch NOTE Before unpacking the switch inspect the container and immediately report any evidence of damage When unpacking the S4200 ON Series S4248FB ON and S4248FBL ON switch make sure that the following items are included One S4200 ON Series S4248FB ON or S4248FBL ON switch One RJ 45 to DB 9 fem...

Page 20: ...le electrical components in a rack ensure that the total component power ratings do not exceed the circuit capabilities Overloaded power sources and extension cords present fire and shock hazards Elevated ambient temperature If you install the switch in a closed rack assembly the operating temperature of the rack environment may be greater than the room ambient temperature Use care not to exceed t...

Page 21: ...ee the installation labels attached to the rail assembly 1 With the ReadyRails flange ears facing outward place one rail between the left and right vertical posts Align and seat the back flange rail pegs in the back vertical post flange In the following illustration item 1 and its extractions show how the pegs appear in both the square and nonthreaded round holes S4200 ON Series installation 21 ...

Page 22: ...allation CAUTION Your switch is not NEBS Earthquake Z4 compliant if you this installation method NOTE For more installation instructions see the installation labels attached to the rail assembly 1 For this installation remove the tool less latch castings from the front side of each ReadyRails assembly see item 1 Use a Torx screwdriver to remove the two screws from each front latch on the switch si...

Page 23: ...r supplied screws see item 3 4 Repeat this procedure for the second rail Two post center mount installation CAUTION Your switch is not NEBS Earthquake Z4 compliant if you this installation method NOTE For more installation instructions see the installation labels attached to the rail assembly 1 Slide the bracket rearward until it clicks into place and secure the rail bracket to the front of the po...

Page 24: ...t you must remove the tool less latch castings described in Step 1 NOTE For more installation instructions see the installation labels attached to the rail assembly 1 For this installation remove the tool less latch castings from the front side of each ReadyRails assembly see item 1 Use a Torx screwdriver to remove the two screws from each front latch on the switch side of the rail Remove the tool...

Page 25: ... configurations slide the switch into the rails in the same manner as the four post configurations 1U front rack installation Configure the rails that are attached to the switch 1 NOTE For more instructions see the installation instruction labels on the rail Attach the inner switch rails to the S4200 ON Series S4248FB ON and S4248FBL ON switch Line up the rail with the mounting heads and attach th...

Page 26: ...e previously mounted ReadyRails and slide the switch in until it is flush with front of rack To keep the switch from inadvertently sliding out of the rack and falling about three inches before you fully insert your switch the rail locking feature engages 26 S4200 ON Series installation ...

Page 27: ... wire NOTE For DC powered switches the only way to safely ground your switch is to attach a dedicated ground wire Depending on the type of switch to attach a ground cable to the switch you need M3 or M4 screws The switch ships with one of the following two configurations One threaded hole using an M3 screw Two threaded holes using one of the two M4 screws In both configurations the ground cable is...

Page 28: ...rning labels and always wear eye protection Never look directly into the end of a terminated or unterminated fiber or connector as it may cause eye damage 1 Position the optic so it is in the correct position The optic has a key that prevents it from being inserted incorrectly 2 Insert the optic into the port until it gently snaps into place NOTE When you cable the ports be sure not to interfere w...

Page 29: ...original packaging place the switch and components on an anti static surface 1 Back up the switch configuration to your back up computer or laptop TFTP server copy running config tftp hostip filepath To establish a console connection to the switch CLI assign an IP address on the switch network 2 Disconnect the power source 3 Label and remove all cables 4 Remove the switch from the rack At the same...

Page 30: ...ical requirements NOTE Connect the power supply to the appropriate branch circuit protection as defined by your local electrical codes and verify that the remote power source complies with the switch input power specifications NOTE If you use a single PSU install a blank plate in the other PSU slot Use power supply 2 PSU2 as the blank plate slot To install the blank plate use a 1 Philips screw dri...

Page 31: ...ng green five times and off there is a PSU mismatch Flashing green system update Off PSU is off AC or DC power supply installation NOTE The PSU slides into the slot smoothly Do not force a PSU into a slot as this action may damage the PSU or the S4200 ON Series switch NOTE Ensure that you correctly install the PSU When you install the PSU correctly the power connector is on the right side of the P...

Page 32: ...e no field serviceable components in the PSU To request a hardware replacement see Dell EMC support NOTE If you use a single PSU install a blank plate in the other PSU slot If you are only using one power supply install the power supply in the first slot PSU1 Install a blank plate in the second slot PSU2 1 Disconnect the power cable from the PSU 2 Use the grab handle to slide the PSU out of the po...

Page 33: ...DC power source wires to the other side of the wiring block See steps 1 and 3 WARNING Do not cross the wires In the wiring block RTN aligns with RTN and 48V aligns with 48V 5 Insert the DC power connector into the power socket of the DC PSU Ensure that the connector pins firmly seat and you hear the click of the power connector s left and right levered clamps lock into place WARNING Never try to f...

Page 34: ...n Airflow is from the I O panel to the PSU normal Airflow is from the PSU to the I O panel reverse Environmental factors can decrease the amount of time required between fan replacements Check the environmental factors regularly An increase in temperature and particulate matter in the air might affect performance for example new equipment installation CAUTION Check the fans at six month intervals ...

Page 35: ... direction reverse or normal If you mix the airflow direction to avoid overheating your switch you must correct the mixed airflow 1 Take the fan module out of the shipping box 2 Slide the module into the bay Figure 20 S4200 ON Series fan modules installation 1 Orange release tab Fan module replacement To request a hardware replacement see Dell EMC support CAUTION Complete the following steps withi...

Page 36: ...s found in GR 63 CORE Minimum dust arrestance of 65 per ASHRAE Standard 52 1 1992 OR Minimum Efficiency Rating Value MERV of 2 per ANSI ASHRAE Standard 52 2 2007 CAUTION For Network Equipment Building Systems NEBS compliance use NEBS approved filters Use fan air filters with reverse blue banded air flow systems PSUs and fans You can replace the air filters individually on each fan within the switc...

Page 37: ...ed to the serial port can support the required 115200 baud rate NOTE Before starting this procedure ensure your PC has a 9 pin serial port You must have a terminal emulation program already installed and running on your PC NOTE If your PC s serial port cannot accept a female DB 9 connector acquire a DB 9 male to male adaptor 1 Install the provided RJ 45 connector side of the provided cable into th...

Page 38: ...y NOTE The following message displays if the USB device is not seen mount mounting dev sdb on mnt usb failed No such device or address 4 OPTIONAL Add a device to the file systems table using the fstab command and mount the file systems ONIE vi etc fstab FSTAB entry for the ONIE BOOT partition mounted on boot LABEL ONIE BOOT mnt onie boot ext4 defaults rw errors remount ro 0 1 dev sdb mnt usb vfat ...

Page 39: ...URL and erases any installed OS During the initial setup the switch boots to ONIE Install ONIE Install boots with ONIE Discovery to the console ONIE ONIE service discovery ONIE attempts to locate the installer through several discovery methods as shown To download and run an installer the ONIE Service Discovery feature uses the first successful method found 1 Pass from the boot loader 2 Search loc...

Page 40: ...53 33 Bcast 10 255 255 255 Mask 255 0 0 0 inet6 addr fe80 92b1 1cff fef4 9c76 64 Scope Link UP BROADCAST RUNNING MULTICAST MTU 1500 Metric 1 RX packets 18 errors 0 dropped 0 overruns 0 frame 0 TX packets 24 errors 0 dropped 0 overruns 0 carrier 0 collisions 0 txqueuelen 1000 RX bytes 1152 1 1 KiB TX bytes 6864 6 7 KiB Interrupt 21 Memory ff300000 ff320000 To assign an IP address to the management ...

Page 41: ... design IEEE standards Agency compliance USA Federal Communications Commission statement European Union EMC directive conformance statement Japan VCCI compliance for class A equipment Korean certification of compliance Electromagnetic compatibility Safety standards and compliance agency certifications Product recycling and disposal Chassis physical design Table 5 Chassis physical design Parameter ...

Page 42: ...ude 10 000 feet 3 048 meters Maximum non operational altitude 39 370 feet 12 000 meters Shock Dell EMC Spec SV0115 Table 7 AC power requirements Parameter Specifications Power supply 100 240 VAC 50 60 Hz Maximum current draw per system 6A 5A at 100 120V AC 3A 2 5A at 200 240V AC Maximum power consumption 600 Watts Typical power consumption 300 Watts Table 8 DC power requirements Parameter Specific...

Page 43: ...d void the user s authority to operate the equipment This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Figure 22 Canadian department of communication statement European Union EMC dire...

Page 44: ...ormation Technology Equipment VCCI If this equipment is used in a domestic environment radio disturbance may arise When such trouble occurs the user may be required to take corrective actions WARNING Use the AC power cords with Dell EMC equipment only Do not use Dell EMC AC power cords with any unauthorized hardware Figure 24 Japan warning label Korean certification of compliance Figure 25 Korean ...

Page 45: ... CFR47 Part 15 Subpart B Class A Immunity EN 300 386 EMC for Network Equipment EN 55024 EN 61000 3 2 Harmonic Current Emissions EN 61000 3 3 Voltage Fluctuations and Flicker EN 61000 4 2 ESD EN 61000 4 3 Radiated Immunity EN 61000 4 4 EFT EN 61000 4 5 Surge EN 61000 4 6 Low Frequency Conducted Immunity Safety standards and compliance agency certifications CUS UL 60950 1 2nd Edition Meets or exceed...

Page 46: ...determines the framework for the return and recycling of used appliances as applicable throughout the European Union This label is applied to various products to indicate that the product is not to be thrown away but rather reclaimed upon end of life per this Directive Figure 27 The European WEEE symbol In accordance with the European WEEE Directive electrical and electronic equipment EEE is to be...

Page 47: ...croll down to the bottom of the web page and select your country from the drop down menu To obtain product specific information enter the 7 character service tag or 11 digit express service code of your switch and click Submit To view the chassis service tag or express service code pull out the luggage tag or enter the show chassis command from the CLI To receive more technical support click Conta...

Reviews: