Part Number: 9291456 11/17
9
Section 2
Installation
N225 & N227 ALTERNATE INSTALLATION DETAILS
NOTE: This installation is not recommended as it will limit
access to the control.
Cabinet Interior Minimum Dimensions
Dimension
N225-E, N225P
N227-E, N227P
A
31.62” (80cm)
31.62” (80cm)
B
21.50” (55cm)
29.62” (75cm)
C
26.00” (66cm)
26.00” (66cm)
D
26.62” (68cm)
26.62” (68cm)
E
16.12” (41cm)
29.62” (75cm)
F
Minimum 5” (13cm), Maximum 7.0” (18cm)
23.50”
(60cm)
9.00”
(23cm)
9.00”
(23cm)
11.12”
(28cm)
Cutout
to match
condenser
face &
control
C
E
D
A
B
12.0”
(30cm)
F
1. Install partitions between drop-in freezer and other
electrical appliances if they are located in the same
cabinet. Partitions must fully extend front to back and
top to bottom.
2. Install a GFCI receptacle a minimum of 14” (36cm) up
from the cabinet bottom inside the partitions. Run the
outlet to a switch. With limited access to the control, a
switch will make it easy to turn the unit off for defrost.
3. Louver cutout must extend to bottom of cabinet.
NOTE: Any restriction to the proper air flow will void the
compressor warranty.
• Louver measures 13.00” x 25.00” (33cm x 64cm).
• Louver Cutout Size is 12.00” x 23.50” (30cm x 60cm)
(typical installation).
• An additional opening in cabinet to permit removal
of heated air is recommended. Cut opening 8”x11”,
a total of 88 square inches (20cm x 28cm, a total of
568 square centimeters).
4. Remove the telescoping duct from the condensing unit.
5. Place the condensing unit through the counter cutout.
6. Construct a 9”x9” air duct (not provided) connecting
the condenser face to the louver.
23.50”
(60cm)
9.00”
(23cm)
9.00”
(23cm)
11.12”
(28cm)
Cutout
to match
condenser
face &
control
C
E
D
A
B
12.0”
(30cm)
F
2.00”
(5cm)
3.00”
(8cm)
9.00”
(23cm)
6.00”
(15cm)
10.00”
(25cm)
0.91” (23mm)
0.50”
(13mm)
0.50” (13mm)
4 X 0.125” (3mm)
2.00” (5cm)
Condenser Face
2.00” (5cm)