DEKKER Vacuum Technologies, Inc. / Part No. 9983-0000-E02 / September 2019
8
CURRENT INPUT/OUTPUT ASSIGNMENTS
Inputs
Digital Inputs
Analog Inputs
RTD Inputs
E-Stop
Vacuum
RTD1 – Aux Temp
Overloads
Backpressure
RTD2 – Discharge Temp
Aux Contact Vac Pump
Circ Pump Pressure
Low Fluid Level
Diff Pressure
High Fluid Level
Remote Start
Remote Stop
Circ Pump Overload
External Warning
Note:
Analog input 4 is a 0-15 psia transducer used in conjunction with Analog input 1 transducer to measure
the difference in vacuum across an inlet filter.
Outputs
Relay Outputs
C1/NO = Vac Pump Motor Starter
C2/NO = Local Lag Light
C3/NO = Horn Output
C4/NO = Remote Lag Light
C5/NO = All Fault Out
C6/NO = Scavenger Valve Out
C7/NO = Cooling Fan