3.6 Digital inputs
Category
Specifications
Controller terminals
33, 34, 35, 36, 37, 38, 39, 40, 41
Number of inputs
9
Type
Negative sensing (connect to ground for activation)
Software configurable options
Emergency stop, Remote start/ stop, and more (see
Controller overview,
Configurable parameters
in the
User manual
for more details).
3.7 Analogue resistive sensor inputs
Category
Specifications
Controller terminals
11 (Oil pressure)
12 (Fuel)
13 (Temperature)
14 (Aux 1)
15 (Aux 2)
Number of inputs
5
Type
Ratio-metric sensing
Range
10 to 5000 Ω
Open circuit detection
Above 5.5 kΩ
Measurement accuracy
±2 % of full scale (up to 1000 Ω)
SCP connection
SCP connections for Analogue inputs 1 to 4*:
Battery
Engine body
Sensor
input
Sensor
common
T erminal 16
Terminal 2
Terminal 1
Supply
SGC 4xx series
Analogue
resistive
sensor
*SCP connections for Analogue input 2 used as
Fuel level sensor
with the reference configured as
Battery Negative
Battery
Sensor
input
Sensor
common
Terminal 2
Terminal 1
Supply
SGC 4xx series
Analogue
resistive
sensor
USER MANUAL 4189341243A UK