Register offset
Value
Scale factor
Unit
Bits/Sign
77
DG status
Controller mode
-
Config (1)
Run (0)
16/16
Mains healthy/unhealthy
-
True (1)
False (0)
15/16
DG operation mode
-
Scheduler-110
Cyclic-111
Auto-101
Manual-100
14-12/16
Load on Mains
-
True (1)
False (0)
11/16
Load on DG
-
True (1)
False (0)
10/16
Current DG status
-
Running
Stopped
9/16
DG stopped normally
-
True (1)
False (0)
8/16
DG stopped with fault
-
True (1)
False (0)
7/16
DG fail to start
-
True (1)
False (0)
6/16
Gen available
-
True (1)
False (0)
5/16
Common shutdown
-
True (1)
False (0)
4/16
Common electric trip
-
True (1)
False (0)
3/16
Common warning
-
True (1)
False (0)
2/16
Common notification
-
True (1)
False (0)
1/16
Communication structure, page 28
Register offset
Value
Scale factor
Unit
Bits/Sign
78-81
Current time stamp
Structure of broadcast message
Byte no.
Byte contents
0
Page ID
1
Data at offset 0 - high byte
2
Data at offset 0 - low byte
3
Data at offset 1 - high byte
4
Data at offset 1 - low byte
5
Data at offset 2 - high byte
6
Data at offset 2 - low byte
7
Reserved
USER MANUAL 4189341243A UK