MIB
Installation Instructions and Reference Handbook
DEIF A/S
Page 34 of 50
Screen no. 7
DO alarm time:
This is the time the alarm has to be present
before DO alarm will be activated.
Time is also “delay” until DO alarm will deactivate
when the alarm is no longer present.
Integer from 0 to 255.
1 digit is 300ms.
to move the cursor one digit at a time
to increase the digit
to decrease the digit
to accept changes and move to next screen
Example: DO = 2 equal to 600ms (2x300ms)
Screen no. 8
DO1 alarm output items:
DO1 alarm output can be one of the items shown
below.
to move the cursor one digit at a time
to increase the digit
to decrease the digit
to accept changes and move to next screen
Example: DO1 alarm output = V31 line voltage
Screen no. 9
DO1 alarm function:
1 = high alarm.
0 = low alarm.
High alarm: Alarm if input exceeds alarm setpoint.
Low alarm: Alarm if input is under alarm setpoint.
to increase the digit
to decrease the digit
to accept changes and move to next screen
Example: DO1 = high alarm