MIB
Installation Instructions and Reference Handbook
DEIF A/S
Page 27 of 50
System parameter setting
The system parameter setting mode is entered by pressing the
and
keys simultaneously in the normal display mode. The setup of the MIB via the
front keys can be protected by an access code. The access code is a 4 digit
number.
The factory default code is 0000.
Functionality of the four push-buttons in the
system mode:
to move the cursor one digit at a time
to increase the digit
to decrease the digit
to accept changes and move to next screen
+
simultaneously to exit the system
mode
Enter the correct access code, default = 0000, press
V/A
to go to the first
parameter setting screen.
Address for communication purpose (only MIB 7000C):
Select the address of the unit, a digit number
from 1-247. Default = 1.
to move the cursor one digit at a time
to increase the digit
to decrease the digit
to accept changes and move to next
screen
Note:
All meters in the same RS485 net should have different addresses
according to the Modbus RTU protocol.
Any change has to be accepted with the V/A key before exiting the
system mode. Otherwise, the change will not be stored.