AL8-2 – Programming manual
4189320003D
Page 8/19
HOW TO PROGRAMME INDIVIDUAL FUNCTIONS (INPUTS 1 TO 8)
Set AL8-2 to programming status:
Press the
PRG
button. This button is slightly countersunk when
compared with the front plate, and a thin, sharp tool like e.g. a small
screwdriver, a needle or the like must be applied to press this button.
Do not use a pencil. The lead may break and fall behind the front plate.
After having pressed the PRG push-button, the LED below the push-
button will be lit (green), indicating that the alarm panel has been set to
the programming status and that programming may be started.
The LED for "DELAY OF ALARM" (i.e. "POWER ON") is switched off
when the unit is set to programming status.
The moment the "PRG" LED is lit (green), the LED for input channel 1 (INPUT 1)
is lit (green) to indicate that this channel may now be programmed.
When pressing the channel selector
CHANNEL SELECT
, the LED for channel 1 (INPUT
1) is switched off and the LED for channel 2 (INPUT 2) is lit (green), etc.
First step of the programming is thus to select input channel. When the requested input
channel is indicated, i.e. the relevant LED is lit (green), the
FUNCTION SELECT
push-
button is pressed.
NOTE: The LED for the selected input channel will continue being lit (green)
throughout the complete programming procedure for the relevant channel.
FUNCTION SELECT points to the individually programmable functions in the following
order:
1: N/O,
N/C
2: OUTPUT A, OUTPUT B
3: INHIBIT
4: CABLE
FAILURE
5: DELAY OF ALARM
I.e., after the first push of FUNCTION SELECT, N/O, N/C is selected.