4.1.21 Slot #6, 4 relay outputs (option M14.6)
Term.
Function
Technical data
Description
90
NE/ND
Relay 90
250 V AC 5 A
Configurable
91
Com.
92
NE/ND
Relay 92
250 V AC 5 A
Configurable
93
Com.
94
NE/ND
Relay 94
250 V AC 5 A
Configurable
95
Com.
96
NE/ND
Relay 96
250 V AC 5 A
Configurable
97
Com.
4.1.22 Slot #6, 4 analogue inputs (option M15.6)
Term.
Function
Technical data
Description
90
Analogue input 91 -
Common
Configurable
91
Analogue input 91 +
4 to 20 mA in
92
Analogue input 93 -
Common
Configurable
93
Analogue input 93 +
4 to 20 mA in
94
Analogue input 95 -
Common
Configurable
95
Analogue input 95 +
4 to 20 mA in
96
Analogue input 97 -
Common
Configurable
97
Analogue input 97 +
4 to 20 mA in
4.1.23 Slot #6, analogue outputs for GOV/AVR or transducer (option F1)
Term.
Function
Description
90
Not used
91
0
Transducer output
92
0(4) to 20 mA
93
Not used
94
Not used
95
0
Transducer output
96
0(4) to 20 mA
97
Not used
AGC-3 installation instructions 4189340728
UK
Hardware
DEIF A/S
Page 34 of 65