4.1.10 Slot #4, relay outputs (option M14.4, standard)
Term.
Function
Technical data
Description
65
NE/ND
Relay 65
250 V AC/5 A
Generator GOV: Increase frequency/configurable
66
Com.
67
NE/ND
Relay 67
250 V AC/5 A
Generator GOV: Decrease frequency/configurable
68
Com.
69
Not used
Relay 69
250 V AC/5 A
Configurable
70
Com.
71
Not used
Relay 71
250 V AC/5 A
Configurable
72
Com.
4.1.11 Slot #4, analogue outputs for GOV/AVR or transducer (option E1)
Term.
Function
Description
65
Not used
66
+/-25 mA
Configurable
67
0
68
Not used
69
Not used
70
+/-25 mA
Configurable
71
0
72
Not used
4.1.12 Slot #4, analogue outputs for GOV/AVR or transducer (option EF2)
Term.
Function
Description
65
Not used
66
+/-25 mA
Configurable
67
0
68
Not used
69
Not used
70
0(4) to 20 mA
Configurable
71
0
72
Not used
AGC-3 installation instructions 4189340728
UK
Hardware
DEIF A/S
Page 29 of 65