4.1.18 Slot #5, AC measuring - AGC mains unit
The I/O list below is for the AGC mains unit.
Term.
Function
Technical data
Description
73
I L1, s1
Mains current L1
x/1 A or x/5 A input
74
I L1, s2
75
I L2, s1
Mains current L2
x/1 A or x/5 A input
76
I L2, s2
77
I L3, s1
Mains current L3
x/1 A or x/5 A input
78
I L3, s2
79
U L1
Mains voltage L1
Max. 690 V AC phase-phase value
80
Not used
81
U L2
Mains voltage L2
Max. 690 V AC phase-phase value
82
Not used
83
U L3
Mains voltage L3
Max. 690 V AC phase-phase value
84
U
NEUTRAL
Mains voltage neutral
85
U L1
Bus voltage L1
Max. 690 V AC phase-phase value
86
Not used
87
U L2
Bus voltage L2
Max. 690 V AC phase-phase value
88
U
NEUTRAL
Bus voltage neutral
89
U L3
Bus voltage L3
Max. 690 V AC phase-phase value
AGC-3 installation instructions 4189340728
UK
Hardware
DEIF A/S
Page 32 of 65