9.1.2 ADJUSTABLE PARAMETERS
Front Panel Configuration Editor
Section
Parameter as shown on display
Factory Settings
DISPLAY
Contrast
53%
Language
English
LCD Page Timer
5m
Auto Scroll Delay
2s
Current Date and time
hh:mm
EDITOR
Module versions V2.0.0+
Alt Config
Default Config
ENGINE
Oil Pressure Low Shutdown
1.03bar
Oil Pressure Low Pre Alarm
1.17bar
Coolant Temperature Low Warning
70ºC
Coolant Temperature High Pre Alarm
90ºC
Coolant Temperature High Shutdown
95ºC
Start Delay Timer
5s
Pre Heat Timer
0s
Crank Duration Timer
10s
Crank Rest Timer
10s
Safety On Delay
10s
Smoke Limiting
0s
Smoke Limiting Off
0s
Warm Up Timer
0s
Cool Down Timer
1m
Engine Under Speed Shutdown
Inactive
Engine Under Speed Shutdown
1260RPM
Engine Under Speed Warning
Inactive
Engine Under Speed Warning
1350RPM
Engine Over Speed Warning
Inactive
Engine Over Speed Warning
1650RPM
Engine Over Speed Shutdown
1710RPM
Engine Speed Overshoot Delay
2s
Engine Speed Overshoot
0s
Fail To Stop Delay
30s
Battery Under Voltage Warning
Active
Battery Under voltage Warning Delay
1m
Battery Under Voltage
10V
Charge Alternator Failure Warning
Active
Battery Over Voltage Warning Delay
1m
Battery Over Voltage Warning
30V
Charge Alternator Failure Warning
Active
Charge Alternator Failure Warning
6V
Droop control
Disable (Compatible engine ECUs only)
Droop control
4% (Compatible engine ECUs only)
GENERATOR
Generator Under Voltage Shutdown
184V
Generator Under Voltage Pre Alarm
196V
Generator Over Voltage Pre Alarm
265V
Generator Over Voltage Shutdown
276V
Generator Under Frequency Shutdown
40Hz
Generator Under Frequency Pre Alarm
42Hz
Generator Over Frequency Pre Alarm
55Hz
Generator Over Frequency Shutdown
57Hz
Full Load Rating
500A
Module versions V2.0.0+
kW Overload Trip
500kW
Delayed Over Current
Active
Delayed Over Current
100%
AC System
3 Phase, 4 Wire
CT Primary
600A
CT Secondary
5A
Generator Transient Delay
0s
MAINS
Mains settings only
applicable to DSE7220 and
DSE7320 controllers.
Mains Under Voltage Trip
184V
Mains Over Voltage Trip
276V
Mains Under Frequency Trip
45Hz
Mains Over Frequency Trip
55Hz
Mains Transient Delay
2s
Return Delay
30s
Mains Transfer Time
0.7s
TIMERS
LCD Page Timer
5m
Auto Scroll Delay
2s
Start Delay Timer
5s
Pre Heat Timer
0s
Crank Duration Timer
10s
Crank Rest Timer
10s
Safety On Delay
10s
Smoke Limiting
0s
Smoke Limiting Off
0s
Warm Up Timer
0s
Cool Down Timer
1m
Speed Overshoot Delay
2s
Fail To Stop Delay
30s
Battery voltage Low Warning Delay
1m
Battery Voltage High Warning Delay
1m
Generator Transient Delay
0s
DSE7220 / DSE7320 only
Mains Transient Delay
2s
Return Delay
30s
DSE7220 / DSE7320 only
Mains Transfer Time
0.7s