![DEEP SEA ELECTRONICS DSECONTROL DSE7000 Series Operator'S Manual Download Page 19](http://html.mh-extra.com/html/deep-sea-electronics/dsecontrol-dse7000-series/dsecontrol-dse7000-series_operators-manual_2463069019.webp)
DSE Model 7000 Series Control & Instrumentation System Operators Manual
Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 2 02/05/2008 ADM
19
4.2 TERMINAL DESCRIPTION
4.2.1 DC SUPPLY, FUEL AND START OUTPUTS
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
1
DC Plant Supply Input
(Negative)
2.5mm²
AWG 13
2
DC Plant Supply Input
(Positive)
2.5 mm²
AWG 13
(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and Output
relays E,F,G & H
3
Emergency Stop Input
2.5mm²
AWG 13
Plant Supply Positive. Also supplies outputs 1 & 2.
(Recommended Maximum Fuse 20A)
4
Output relay A (FUEL)
2.5mm²
AWG 13
Plant Supply Positive from terminal 3. 15 Amp rated.
Fixed as FUEL relay if electronic engine is not configured.
5
Output relay B (START)
2.5mm²
AWG 13
Plant Supply Positive from terminal 3. 15 Amp rated.
Fixed as START relay if electronic engine is not configured.
6
Charge fail / excite
2.5mm²
AWG 13
Do not connect to ground (battery negative).
If charge alternator is not fitted, leave this terminal
disconnected.
7
Functional Earth
2.5mm²
AWG 13
Connect to a good clean earth point.
8
Output relay E
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
9
Output relay F
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
10
Output relay G
1.0mm²
AWG 18
Plant Supply Positive. from terminal 2. 3 Amp rated.
11
Output relay H
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
NOTE:- Terminals 12 to 14 are not fitted to the DSE7200/DSE7300 series controller.
NOTE:- When the module is configured for operation with an electronic engine, FUEL and START
output requirements may be different. Refer to Electronic Engines and DSE Wiring for further information.
Part No. 057-004.
4.2.2 ANALOGUE SENSOR
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
15
Sensor Common Return
0.5mm²
AWG 20
Return feed for sensors*
16
Oil Pressure Input
0.5mm²
AWG 20
Connect to Oil pressure sensor
17
Coolant Temperature Input
0.5mm²
AWG 20
Connect to Coolant Temperature sensor
18
Fuel Level input
0.5mm²
AWG 20
Connect to Fuel Level sensor
19
Flexible sensor
(not available on 7200 series controller)
0.5mm²
AWG 20
Connect to additional sensor (user configurable)
NOTE:- Terminals 20 and 21 are not fitted to the 7200/7300 series controller.
NOTE*:- If using single terminal sensors refer to the Appendix section entitled “Sensor wiring
recommendations” elsewhere in this manual.