DSE Model 5520 Automatic Mains Failure Control and Instrumentation System Operators Manual
5520 OPERATING MANUAL ISSUE 1 04/02/05 AM
51
5.4.6 VOLVO TAD9 / TAD16
PLUG
“A”
8
WAY
55xx PIN No
55xx DESCRIPTION
Volvo TAD9/16
EDC III connector
NOTES
6
Aux output 1
Conf
i
gur
e
t
o
“ECU
STOP”
6
TAD9/16 STOP input.
7
Aux output 2
Conf
i
gur
e
t
o
“ECU
POWER”
5
TAD9/16 START input.
3
DC Supply negative
4
DC Supply positive
PLUG
“C”
9
WAY
55xx
PIN No
55xx
DESCRIPTION
Volvo TAD9/16
EDC III connector
NOTES
23
CANbus common
-
Screen for the J1939 cable. Connect at
55xx end only.
24
CANbus H
1 (Hi)
J1939 + Use only screened 120
impedance cable approved specifically
for use in CANbus applications.
25
CANbus L
2 (Lo)
J1939
–
Use
onl
y
scr
eened
120
impedance cable approved specifically
for use in CANbus applications.