DSE Model 5520 Automatic Mains Failure Control and Instrumentation System Operators Manual
5520 OPERATING MANUAL ISSUE 1 04/02/05 AM
47
5.4.2 DEUTZ EMR2
PLUG
“A”
8
WAY
55xx
PIN
No
55xx
DESCRIPTION
Deutz Vehicle side (F)
connector
NOTES
5
Crank output
Connects directly to engine starter
solenoid.
6
Aux output 1
Use to control a 30A
external slave relay to
supply DC battery power to
pin 14. Fuse at 16 amps.
Using 5xxx select the relevant
engi
ne
and
conf
i
gur
e
55xx
‘
aux
out
put
1’
t
o
be
“Enabl
e
ECU”
1
Connects directly to battery
negative
PLUG
“C”
9
WAY
55xx
PIN
No
55xx
DESCRIPTION
Deutz Vehicle side (F)
connector
NOTES
23
CANbus
common
-
Screen for the J1939 cable.
Connect at 55xx end only.
24
CANbus H
12
J1939 + Use only screened 120
impedance cable approved
specifically for use in CANbus
applications.
25
CANbus L
13
J1939 - Use only screened 120
impedance cable approved
specifically for use in CANbus
applications.