Error
code
Description
Probable causes
Checking / solution
e[02
The exchanger sensor is short
circuited
Bad connection
4
Check the wiring between the PCU PCB and the
sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
e[03
The exchanger sensor is on an
open circuit
Bad connection
4
Check the wiring between the PCU PCB and the
sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
e[04
Temperature of heat exchanger
too low
Bad connection
4
Check the wiring between the PCU PCB and the
sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
e[05
Exchanger temperature too high
Bad connection
4
Check the wiring between the PCU PCB and the
sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
e[06
The return temperature sensor has
short-circuited
Bad connection
4
Check the wiring between the PCU PCB and the
sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
e[07
The return temperature sensor is
on an open circuit
Bad connection
4
Check the wiring between the PCU PCB and the
sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
6. Troubleshooting
IniControl For C 330 / C 630 ECO
31
260216 - 7600717-001-06