4. The start-up cycle begins and cannot be interrupted. During the
start-up cycle, the display shows the following information:
A short test where all segments of the display are visible.
fK[xx
: Software version
pK[xx
: Parameter version
The version numbers are displayed alternately.
By pressing the
S
key for a short time, the current operating status
is shown on the display:
Heat demand
Heat demand stopped
1
: Fan ON
5
: Burner stop
"
: Boiler is igniting
6
: Post-circulation of the pump
3
: Heating System
0
: Standby
In STAND-BY, the display normally shows the water pressure next to
0
(only when the hydraulic pressure sensor is connected) and the
symbols
d
and
H
.
Error during the start-up procedure:
4
No information is shown on the display:
-
Check the mains supply voltage
-
Check the main fuses
-
Check the fuses on the control panel:
(F1 = 2 AT, F2 = 8 AT)
-
Check the connection of the mains lead to the connector in the
instrument box
4
A fault is indicated on the display by the fault symbol
a
and a
flashing fault code.
-
The meaning of the error codes is given in the error table.
-
Press for 3 seconds on key
J
to restart the boiler.
5.3
Reading out measured values
For operation of the boiler
C630 Eco
: The features and
instructions described are for each boiler module.
5.3.1.
Reading out measured values
The following current values can be read off the information menu
Q
:
4
5200
= Fan speed.
4
5201
= Fan speed Set point.
4
5203
= Burner flame signal.
4
5204
= Gas valve open (1) or closed (0).
4
5205
= GpS connected.
4
5206
= Ignition phase.
4
5207
= Ionization current.
4
5208
= Heat output requested.
4
5209
= Release input.
IniControl For C 330 / C 630 ECO
5. Commissioning
260216 - 7600717-001-06
16