5.3.3.
Status and sub-status
The information menu
Q
gives the following status and sub-status
numbers:
St
status
Sub-status Operation
0
Rest
0
Rest
1
Boiler start (Heat demand)
1
Anti-short cycle activated
2
Open isolating valve
3
Start-up of the boiler pump
4
Wait for the correct temperatures for burner start
2
Burner start
10
Open gas valve (External)
11
Fan start-up
12
Opening of the flue gas flue damper
13
Preventilation
14
Awaiting closure of the RL contact (if the function is activated)
15
Burner on switch request
16
Leak proofing system test
17
Pre-ignition
18
Ignition
19
Check flame presence
20
Inter-ignition time delay
3
Boiler on heating service
30
Nominal internal set point
31
Limited internal set point
32
Output control
33
Temperature protection gradient level 1 (Modulate down)
34
Temperature protection gradient level 2 (Part load)
35
Temperature protection gradient level 3 (Blockage)
36
Modulate up for flame control
37
Temperature stabilisation time
38
Cold start
5
Burner stop
40
Burner shutdown request
41
Post-ventilation
42
Fan speed reduction
43
Closure of the flue gas flue damper
44
Stop fan
45
Output restricted by flue gas temperature
6
Switching off the boiler
60
Post-operation time delay on the boiler pump
61
Stop boiler pump
62
Close isolating valve
63
Start anti short cycle
8
Control stop
0
Awaiting burner start-up
1
Anti-short cycle activated
9
Blocking
XX
Shutdown code XX
10 Lock out
11 Chimney-sweeping position: Low speed
12 Chimney-sweeping position: CH speed
13 Chimney-sweeping position: DHW speed
IniControl For C 330 / C 630 ECO
5. Commissioning
260216 - 7600717-001-06
18