DTG 1300 Eco.NOx/V
Incidents and solutions
Symptoms
Probable causes
Solution
The heater does not start
and the safety box is not
affected (red alarm
indicator off)
- The heater thermostat is
requiring heat
- Create a demand by moving the heater thermostat or the setting level
(option).
- Setting (option) is not requiring
heat.
- The safety thermostat has been
triggered after overheating.
- Solve the cause of overheating and reset the safety thermostat.
- No current
- Place the Stop/Start switch on "On"
The burner does not
ignite and the safety box
is not affected (red alarm
indicator off)
- On safety because of a lack of
gas
- Purge the gas supply pipe then reset the heater using the panel reset
button
- Faulty gas valve
- Check the gas valve and replace if necessary.
- No spark from the electrode
- Check the electric cable connection to the safety box and the electrode
- No ionisation current
- Check the ionisation probe and earth wire connection.
- Check the position of the ionisation probe and the flame diffuser in the
ignition burner
- Blocked filter or ignition burner
injector
- Clean the filter and the ignition burner injector
The burner ignites and
the safety box goes into
standby (burner cut and
the alarm indicator
flashes)
- Anti-blowback thermostat cut
- Check the draught in the chimney connection, check the condition of the
anti-blowback thermostat, then press the Start/Stop button to cancel the 15
timer and restart the heater
- Please note the seriousness of unplanned intervention on the combustion
product evacuation checking device : evacuation faults must be solved by
improving the draught in the chimney.
- In the event of a thermostat fault, it must be replaced by a part stated on
our "Spare parts list". Its position must not be modified, which is defined by
the 2 bosses on the holding bracket which are located in the 2 holes on the
draught diverter. The thermostat must not be placed out of service.
The burner ignites and
the safety box is affected
(alarm indicator on)
- Inversion of the phase and
neutral wires on the heater's
command panel
- Connect the phase to terminal 1 and neutral to 2.
The burner ignites but
with reduced power
- Upstream pressure too weak
- Check gas supply
- Dirty filter
- Clean the filter
- Unsuitable injectors (See Table
"Pressure setting and marking of
calibrated injectors")
- Check them
- Faulty gas valve
- Check gas valve and replace if necessary
- Injectors too small
- Check them (See Table "Pressure setting and marking of calibrated
injectors")
Dirty cast iron body
(hearth)
- Upstream pressure too high
- Revoir l’alimentation en gaz
- Dirty burner
- Clean the burner
- Insufficient or poorly placed air
supply
- Enlarge air supply, smoothen airation holes
- Faulty gas valve
- Check gas valve and replace if necessary
Noisy heater
- Poor purge
- Purger correctement
- Body has scale
- Détartrer le circuit chauffage
- Unsuitable injectors (Whistling) - Check injectors
- Burner clogged by building dust
Summary of Contents for Elitec DTG 1304 Eco.NOx/V
Page 1: ...DTG 1300 Eco NOx V Gas fired boilers English 23 06 05 Elitec Technical instructions...
Page 31: ...31 23 06 05 300002940 001B DTG 1300 Eco NOx V Gas line Cladding...
Page 32: ...32 DTG 1300 Eco NOx V 23 06 05 300002940 001B Linking kit...
Page 36: ...36 DTG 1300 Eco NOx V 23 06 05 300002940 001B...
Page 37: ...DTG 1300 Eco NOx V 23 06 05 300002940 001B...
Page 38: ...DTG 1300 Eco NOx V 23 06 05 300002940 001B...