![DeDietrich Elitec DTG 1304 Eco.NOx/V Technical Instructions Download Page 24](http://html1.mh-extra.com/html/dedietrich/elitec-dtg-1304-eco-nox-v/elitec-dtg-1304-eco-nox-v_technical-instructions_2462437024.webp)
24
DTG 1300 Eco.NOx/V
23/06/05 - 300002940-001B
Maintenance
1 Cleaning main burner and ignition burner
The main burner and the ignition burner injector with its filter must be
regularly cleaned to ensure good performance. Il est conseillé de le
faire au moins 1 fois par an.
Main burner
Switch off the boiler electrical power supply
Cut the gas supply.
Open the heater door
Disconnect the burner connector under the command panel
Unscrew the union joint on the gas inlet pipe
Unscrew the screws
Take out the burner earth wire
Disassemble the burner drawer
Clean the burner with a brush, a vacuum cleaner or a blower
Do not use a metal brush !
- Re-assemble the burner earth wire
Ignition burner
Unscrew the connecting screw, then pull the gas supply pipe
towards you
Take out the injector and the filter
Remove ionisation probe
1
and the earth electrode
4
deposits
(for example using sand paper)
- Re-attach the supply tube (14 spanner),
- Check the position of the ionisation probe
1
, the ignition electrode
gap
2
and the position of the flame diffuser
3
in terms of the sizes
indicated on the drawing (required in the event of heater
malfunction).
Check the seals for the gas.
1
Ionisation probe
2
Ignition electrode
3
Flame diffuser
4
Earth electrode
Summary of Contents for Elitec DTG 1304 Eco.NOx/V
Page 1: ...DTG 1300 Eco NOx V Gas fired boilers English 23 06 05 Elitec Technical instructions...
Page 31: ...31 23 06 05 300002940 001B DTG 1300 Eco NOx V Gas line Cladding...
Page 32: ...32 DTG 1300 Eco NOx V 23 06 05 300002940 001B Linking kit...
Page 36: ...36 DTG 1300 Eco NOx V 23 06 05 300002940 001B...
Page 37: ...DTG 1300 Eco NOx V 23 06 05 300002940 001B...
Page 38: ...DTG 1300 Eco NOx V 23 06 05 300002940 001B...