Product name
AWHP 8 MR-2 AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Rated heat output under warmer conditions
Prated
kW
6
8
13
Declared capacity for heating for part load at an
indoor temperature of 20 °C and outdoor temper
ature
T
j
T
j
= -7 °C
Pdh
kW
5.6
5.9
9.0
T
j
= +2 °C
Pdh
kW
2.9
5.3
6.5
T
j
= +7 °C
Pdh
kW
6.4
9.0
12.9
T
j
= +12 °C
Pdh
kW
4.3
7.7
10.0
T
j
= bivalent temperature
Pdh
kW
5.6
6.3
8.8
T
j
= operation limit temperature
Pdh
kW
5.6
6.3
8.8
Bivalent temperature
T
biv
°C
-10
-10
-10
Cdh
—
1.0
1.0
1.0
Seasonal space heating energy efficiency under
average conditions
ƞ
s
%
129
125
121
Seasonal space heating energy efficiency under
colder conditions
ƞ
s
%
119
113
113
Seasonal space heating energy efficiency under
warmer conditions
ƞ
s
%
169
167
161
Declared coefficient of performance or primary
energy ratio for part load at an indoor tempera
ture of 20 °C and outdoor temperature
T
j
T
j
= -7 °C
COPd
-
1.95
1.87
1.85
T
j
= +2 °C
COPd
-
3.22
3.17
3.02
T
j
= +7 °C
COPd
-
4.57
4.54
4.34
T
j
= +12 °C
COPd
-
6.55
6.19
5.75
T
j
= bivalent temperature
COPd
-
1.70
1.20
1.35
T
j
= operation limit temperature
COPd
-
1.70
1.20
1.35
Operation limit temperature for air-to-water
heat pumps
TOL
°C
-10
-10
-10
Heating water operating limit temperature
WTOL
°C
60
60
60
Electrical power consumption
Off mode
P
OFF
kW
0.009
0.009
0.009
Thermostat-off mode
P
TO
kW
0.049
0.023
0.035
Stand-by
P
SB
kW
0.015
0.021
0.021
Crankcase heater mode
P
CK
kW
0.055
0.055
0.055
Supplementary heater
Rated heat output
Psup
kW
0.0
0.0
0.0
Type of energy input
Electricity
Electricity
Electricity
Other specifications
Capacity control
Variable
Variable
Variable
Sound power level, indoors - outdoors
L
WA
dB
53 - 67
53 - 69
53 - 69
Annual energy consumption under average
conditions
Q
HE
kWh
3499
3999
5861
Annual energy consumption under colder con
ditions
Q
HE
kWh
4621
3804
5684
3 Technical specifications
16