Product name
AWHP 4.5 MR
AWHP 6 MR-3
Seasonal space heating energy efficiency under
average conditions
ƞ
s
%
134
138
Seasonal space heating energy efficiency under
colder conditions
ƞ
s
%
109
116
Seasonal space heating energy efficiency under
warmer conditions
ƞ
s
%
179
172
Declared coefficient of performance or primary
energy ratio for part load at an indoor tempera
ture of 20 °C and outdoor temperature
T
j
T
j
= -7 °C
COPd
-
1.64
1.89
T
j
= +2 °C
COPd
-
3.46
3.53
T
j
= +7 °C
COPd
-
4.96
4.74
T
j
= +12 °C
COPd
-
7.90
7.08
T
j
= bivalent temperature
COPd
-
1.20
1.52
T
j
= operation limit temperature
COPd
-
1.20
1.52
Operation limit temperature for air-to-water
heat pumps
TOL
°C
-10
-10
Heating water operating limit temperature
WTOL
°C
55
60
Electrical power consumption
Off mode
P
OFF
kW
0.009
0.009
Thermostat-off mode
P
TO
kW
0.049
0.049
Stand-by
P
SB
kW
0.009
0.015
Crankcase heater mode
P
CK
kW
0.000
0.055
Supplementary heater
Rated heat output
Psup
kW
0.0
0.0
Type of energy input
Electricity
Electricity
Other specifications
Capacity control
Variable
Variable
Sound power level, indoors - outdoors
L
WA
dB
53 - 61
48 - 65
Annual energy consumption under average
conditions
Q
HE
kWh
2353
2124
Annual energy consumption under colder con
ditions
Q
HE
kWh
4483
3721
Annual energy consumption under warmer
conditions
Q
HE
kWh
1249
1492
Rated air flow rate, outdoors for air-to-water
heat pumps
—
m
3
/h
2680
2700
(1) The rated heat output
Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
(2) If
Cdh is not determined by measurement, the default degradation coefficient is Cdh = 0.9.
Tab.12 Technical parameters for heat pump combination heaters (parameters declared for medium-temperature application)
Product name
AWHP 8 MR-2 AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Air-to-water heat pump
Yes
Yes
Yes
Water-to-water heat pump
No
No
No
Brine-to-water heat pump
No
No
No
Low-temperature heat pump
No
No
No
Equipped with a supplementary heater
Yes
Yes
Yes
Heat pump combination heater
No
No
No
Rated heat output under average conditions
Prated
kW
6
6
9
Rated heat output under colder conditions
Prated
kW
6
4
7
3 Technical specifications
7685690 - v04 - 06042020
AWHP MIV-S
15