30
5.1 ELECTRICAL CONNECTIONS FOR THE SPACE MODEL
! Risk of malfunction due to improper installation !
! Risk of personal injury and property damage due to electric shocks !
Execute the wiring following the directions of “Table 1” and diagram (Pag. 31).
WARNING
To ensure an appropriate level of electrical safety always keep the 230V power supply cables apart (minimum 4mm in the
open or 1 mm through insulation) from low voltage cables (motors power supply, controls, electric locks, aerial and auxiliary circuits
power supply), and fasten the latter with appropriate clamps near the terminal boards
.
WARNING
Connect to the power supply 230 V ~± 10% 50 Hz through a multi pole switch or a different device that can ensure multi pole
disconnection from the power supply, with a contact opening of 3 mm.
Table 1 “terminal board connections”
1-2-3-4
Motor 1 encoder output
5-6
Motor 1 output max 5A
7-8
7 (+)
Configurable 24V
output 1 max 5W (see P066 for values that can be selected)
8 (-)
9-13
9 - N.O.
Input 4. Unused
If
the
installation
req
uires
dif
ferent
commands
and / or
additional
to the
standar
d,
you
can
configure
each
in
-
put t
o the req
uired rat
e.
R
ef
er t
o Chap
ter
“
Adv
anced Programming”.
13 - Com
10-13
10 - N.O.
Input 3. Unused
13 - Com
11-13
11 - N.O.
Input 2 START. In case of intervention it provokes: the operator opening or closing. It
may operate as “inversion” mode (P049=0) or “step by step” mode (P049=1).
13 - Com
12-13
12 - N.C.
Input 1 PHOTO 1. When enabled (see parameter P050 in the table), activation of
PHOTO 1 provokes: an inversion of direction (during closing), the arrest of the move
-
ment (during opening), prevent the start (gate closed).
If unused, short circuit
.
13 - Com
14-15
14 (-)
Stabilized 24 V
power supply output for tested safety devices
max 200mA
15 (+)
16-17
16 (+)
Configurable 24V
output 2 max 5W (see P062 for values that can be selected)
17 (-)
18
Aerial signal input
19
Ground aerial input
CON 1
Connection of motors metallic parts
CON 2
25 V ~ transformer power supply input
CON 3
Courtesy light output
CON 4
Input for NET-NODE / MEMONET connector
CON 5
Input for NET-EXP connector
J4 (jumper)
Operating mode selection jumper:
(closed) = Normal functioning;
(open) = Programming mode;