background image

 

 

NOTE 1: MAXIMUM AMBIENT TEMPERATURE FOR INSTALLATION, 104 F. 
NOTE 2: FOR AUTOMOTIVE USE ONLY, NO MOTORCYCLES, BICYCLES OR PEDESTRIANS. 
NOTE 3: HEATER OPTION MUST BE USED IF TEMP IS (15F) OR BELOW TEMPERATURES. 

 

CONDUITS 

 

  Conduits should be restricted to fit the 3.5"x3.5" opening in pedestal base. Location on pad should be 
centered and spaced approximately  6" from edge of pad on drive way side ( in order to get the most reach out 
of arm ). Conduits to be included should be 120 VAC main power, low voltage control wiring and one or two 
extra for loop sensor leads. Conduit size should be limited to .5" when possible to reduce crowding if more 
than four are needed.  All conduits must be U.L. approved. 

 

WIRING AND HOOKUP

 (Only by a qualified electrician/installer!) 

 

120 VAC 

 

 

Be sure your main power (120vac) is OFF before attempting hookup. The 120 volts AC  supply should be 
terminated to the wires in top of the 4"x4" tube at the top of the chassis. Connect the 120 VAC to BLACK wire, 
Neutral to the WHITE wire and Ground the GREEN wire. 

 Warning- Do not connect any 120 VAC wires 

directly to the terminal strips on the electronic control board. 

 Only U.L. approved 14 AWG ( or larger) 

600 volt insulated wire should be used. A separate UL approved 10 amp circuit breaker should be used for 
each MEGA-ARM operator. 

BATTERIES MUST BE INSTALLED AFTER 120VAC POWER IS TURNED ON.

 

See BATTERY at page 3 and 120 VAC wiring on page 4. 

 

INPUT COMMANDS  

 

Control wire connections at low voltage terminal strip will be at the top of the electronic control board. Make 
connections to the appropriate points for the desired operation. Wires should be U.L. approved 600 volt rated 
and at least 18 awg. They are to be routed through the upper grommet in chassis to avoid chafing. All external 
control devices must have normally open dry contacts. 

DO NOT CONNECT ANY DEVICE WHICH WOULD 

DELIVER ANY VOLTAGE OF ANY KIND TO THESE TERMINALS.

  

Terminals 9, 10, 11, 12 are the commons (0 VDC) used to activate the following inputs. 

 

1, 2, 3 OPEN

These inputs will trigger gate open when pulsed or hold gate open with maintained contact. 

When released gate will close if closing timer is on or if close input is given. 

 

4, AUXILIARY OPEN

 

- Same as 1,2 and 3 with S2 switch 6 off. With S2 switch 6 on, this input will memorize 

multiple vehicles and not allow gate to close until the final vehicle in memory crosses the close loop. Use with 
laser scanners or card readers and (transmitters with timed anti-pass back). With S1 switch 5 on, this input 
becomes a momentary 

pulse open, pulse close. 

 

 

NOTE: Insert a jumper across the JP2 terminal to allow the interlock feature (see page 5 & 14) to work with the 
multiple vehicle memory count selection, use the K1 relay to open the interlocked gate (S1-5 off, S2-6 on, 
jumper across JP2). This allows gate to store input counts via J5 #4 but not raise the arm until the interlocked 
slide or swing gate has fully opened. 

 

5, SAFETY

- This input is generally not used with the MEGA-ARM. If used its function is to make gate reverse 

and go back to the open position if it was closing. Input is disabled when gate is closed. 

  

 

6, CLOSE

When used with a vehicle detector, it is recommended that the presence contacts (N.O. & C.)  be 

used for the close input. This input will close gate after input is applied and then removed. It will stop the open 
cycle and reverse gate to close. (Example:  Car crosses over close loop before arm reaches full open position- 
gate will reverse and close). (Note: The close input also acts as a safety-stop in that if gate is closing and a 
tailgater is sensed at the close input, the gate WILL STOP its closing motion and not continue to close until the 
close input is removed or gate is re-opened).   

  
 

PAGE 2

 

 
 

Summary of Contents for MEGA ARM

Page 1: ... COVERS THE NEW INTER LOCK MEMORY FEATURES WARNING CHILDREN SHOULD NEVER BE ALLOWED TO PLAY NEAR OR OPERATE AUTOMATIC GATES FAILURE TO OBSERVE SAFE OPERATING PROCEDURE TRAIN YOUR CUSTOMER PROPERLY OR INSTALL PROPER WARNING SIGNAGE MAY RESULT IN SERIOUS INJURY DC SOLUTIONS INC 590 SAWGRASS CORPORATE PARKWAY SUNRISE FLORIDA 33325 PHONE 954 846 9488 FAX 954 846 9464 MEGA ARM MEGA PULSE MEGA SENSE MEG...

Page 2: ...1 S2 MODE SELECTIONS S1 5 MODE SELECTIONS S2 5 CLOSE TIMER SELECTION S2 5 ADJUSTMENTS INSTANT REVERSE DEVICE IRD 6 GATE ARM LEVELING 6 TROUBLE SHOOTING AND MAINTENANCE PROCEDURES BATTERY CHECK OUT 7 GATE NOT OPERATING 7 GENERAL SERVICE 7 SHEAR PIN REPLACEMENT 6 SAMPLE CONFIGURATIONS FREE EXIT OPERATION 8 ENTRY WITH ACCESS CONTROL DEVICE 8 DUAL DIRECTION 8 INTERLOCK MEGA ARMS OR WITH OTHER OPERATOR...

Page 3: ...tch dog reset timer State of the art MOSFET motor drive technology NO contactors or relays Dynamic motor braking to preserve arm positioning Soft start and stop in open and close travel motions No limit switches to fail uses magnetic Hall Effect sensors to monitor arm position Maximum Run Timer for motor MRT with anti tamper protection in closing direction Each unit configurable as master or slave...

Page 4: ... external control devices must have normally open dry contacts DO NOT CONNECT ANY DEVICE WHICH WOULD DELIVER ANY VOLTAGE OF ANY KIND TO THESE TERMINALS Terminals 9 10 11 12 are the commons 0 VDC used to activate the following inputs 1 2 3 OPEN These inputs will trigger gate open when pulsed or hold gate open with maintained contact When released gate will close if closing timer is on or if close i...

Page 5: ...iver RELAY OUTPUT K1 OPTION S1 6 off S1 8 off relay will fire latch when gate is not closed S1 6 on S1 8 off relay will fire when arm is pushed up off of limit switch use with slip clutch option and fires relay when a tail gate is detected by the close loop ANTI TAIL GATE ALARM S1 6 off S1 8 on relay will pulse relay when arm reaches full open position S1 6 on S1 8 on relay will only pulse when in...

Page 6: ...ster gate J5 terminal 12 to slave gate J5 terminal 12 EXAMPLE If only open and close are used at master then three wires will run between gates 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 MASTER J5 SLAVE J5 OPEN CLOSE COMMON EXAMPLE STEP 3 If it is required that if one gate senses an obstruction the other reverses also then 3 additional wires must be run between the master J3 and slave J...

Page 7: ... the obstruction sensor has reversed and re opened the arm or if the S2 7 timer to close is turned on The default will keep the gate up for 4 seconds to allow the vehicle to be moved from the gate arm path Changing settings 1 5 will increase or decrease this hold open time The default of 3 ON and 1 2 4 5 OFF will provide a 4 second close time delay SECONDS 1 2 4 8 16 S2 1 2 3 4 5 6 7 8 SHOWS DEFAU...

Page 8: ...ed this can be done through adjustment to the magnetic cam arm Note that during these adjustments the arm only travels approximately 85 to 89 degrees for its full motion Always adjust for a level arm in the HORIZONTAL POSITION There is a small set screw in the side of the cam arm which can be loosened to allow the cam arm magnet to reach the close limit sensor located on back of controller H2 earl...

Page 9: ...ts are wired correctly test S 3 manual open switch GATE DEAD NO OPERATION 1 Check LED D14 for AC power indication and check AC power switch is on 2 Check LED D11 for Heart Beat pulses if none and D14 AC D5 Brake are on then gate has repeatedly sensed obstructions Clear obstruction then clear with next new input 3 IRD D2 LED is flashing MRT has expired H1 H2 Hall sensors and clearance to magnet on ...

Page 10: ...E LOOP GATE WILL STOP ITS CLOSING MOTION UNTIL LOOP IS CLEARED AGAIN DUAL DIRECTION IS A COMBONATION OF BOTH OF THE ABOVE CONFIGURATIONS TO PROVIDE THE ABILITY FOR TRAFFIC TO ENTER OR EXIT IN THE SAME LANE TERMINAL 7 IS BACKAWAY FREE EXIT TERMINAL 6 IS CLOSE INPUT TERMINAL 6 IS CLOSE INPUT TERMINAL 1 2 3 ARE OPEN INPUTS BACK AWAY LOOP FREE EXIT BACK AWAY LOOP FREE EXIT CLOSE LOOP SPACE BETWEEN LOO...

Page 11: ...F4 F3 IRD AND MRT U3 OVER DRIVE CPU 1 C 2 NC 3 NO 4 24VDC REGULATED TX BLK RED YEL YEL BLU ORG Q3 Q4 Q5 Q6 RELAY OPTIONAL MODE 5 8 I O INTERFACE PORT 24VDC REQULATED 1 AMP DC F1 J5 ACCESSORY POWER IS 24VDC REGULATED RATED AT 500 ma 1 2 AMP POWER AT ACCESSORY AND AT RELAY PIN 4 IS FUSED AT F1 WITH A 1 AMP FAST BLO FUSE NOTE J5 8 IS NOW THE INTERLOCK WITH MEMORY INPUT SEE PAGE 13 D11 HEART BEAT SHOW...

Page 12: ...1 MAGNET 12 MA 012 CAM ARM 13 MA 013 SHEAR PIN 14 MA 014 BOLT NUT 4 MOTOR 15 MA 015 TRANSFORMER 110 220 VAC 24VAC 16 MA 016 MAIN POWER CONNECTION BOX 17 MA 017 BOLT NUT 4 REDUCER 18 MA 018 GROMMET 2 19 MA 019 117 VAC ON OFF SWITCH MA 020 UNIT COVER MA 021 NYLON ARM NUTS 2 MA 022 ARM BOLTS 2 MA 023 GATE ARM 12 FT 20 MA 036 COLLAR 21 MA 037 NYLON WASHER PARTS NOT SHOWN PARTS SHIPPED 1 MEGA ARM OPERA...

Page 13: ...HE STEPS ABOVE THE CAM ARM WHICH ADJUSTS THE LIMITING POINTS OF THE ARMS TRAVEL MUST BE TURNED 90 DEGREES TO THE LEFT WHEN VIEWED WHILE STANDING IN FRONT OF THE CONTROL BOARD CAM ARM NOW POINTS IN THE DIRECTION OF THE ARM AND IS LEVEL WITH MOUNT BRACKET NOTE THE SMALL LIMIT SENSORS ON THE BACK OF THE PCB STEP 4 NOW CHECK TO MAKE SURE THAT S1 7 IS ON MOTOR WIRES ARE REVERSED THE CAM IS ADJUSTED AND...

Page 14: ...INCHES 41 5 17 5 20 25 15 75 41 5 8 0 20 25 13 5 9 0 4 21 5 3 5 3 5 3 5 FOOT PRINT OF BASE ON PAD 9 0 34 75 36 5 8 0 INSIDE POST 5 5 5 5 5 PAD 24x24 6 0 3 25 12 0 12 0 THESE DIMENSIONS WILL CENTER THE OPERATOR ON THE PAD CENTER LINE 2 0 8 0 PAGE 12 ...

Page 15: ...MENSIONS MEASURMENTS ARE IN INCHES 42 0 3 5 FOOT PRINT OF BASE ON PAD 36 5 PAD 24x24X24 SIDE VIEW 14 20 42 0 13 50 13 50 24 0 24 0 DOOR 10 25 8 25 OPEN AREA IN BASE GATE ARM BRACKET 7 125 7 125 14 20 13 50 FOR CONDUIT 12 20 9 90 3 50 PAGE 13 ...

Page 16: ...es from the MEGA ARMs K1 relay common normally open to the other operators common and open input WARNING max of 30 VOLTS 5 AMPS THROUGH RELAY J5 8 was the unused SHADOW LOOP input on the MEGA ARM Note A separate open device 24 hour timer toggle switch can be run to the other operator to control it without raising the gate arm Tampering with the other operators safety loops safety edges and reverse...

Page 17: ... suitable for a particular purpose In no event shall DC Solutions inc be held liable for direct indirect incidental special consequential damages or loss of profits whether based on contract tort or any other legal theory during the course of the warranty or at any time there after The installer and or end user agree to assume all responsibility for all liability in use of this product releasing D...

Reviews: