26
•
When the water tank or ambient temperature sensor are faulty, electric heating
operation is not allowed. “11E”, “12E”, “13E” ", "14E", "15E", "17E", "18E", "19E". are
correspondingly displayed when the coil temperature sensor, ambient temperature
sensor, exhaust temperature sensor, inlet water temperature sensor/tank temperature
sensor, absorb temperature sensor, and outlet water temperature sensor/return water
temperature sensor are faulty.
•
“09E” is displayed when the communication between the main control board and the
wire controller is abnormal or the data line is not connected normally. “--:--” is
displayed when the valid clock cannot be obtained.
•
The communication indicator of the main control board flashes.
•
The buzzer sounds when an alarm occurs.
•
Press any key to silence the alarm.
The fault code table is as follows:
Error Code
Name
01E
Water flow switch disconnected (water cycle heat pump)
02E
03E
04E
09E
11E
12E
13E
14E
15E
17E
18E
19E
20E
21E
Exhaust temperature too high
High pressure switch failure
Low pressure switch failure
Communication failure
Evaporator coil temperature sensor failure
Ambient temperature sensor failure
Exhaust temperature sensor failure
Water inlet temperature sensor failure
Tank temperature sensor failure
Absorb temperature sensor failure
Water outlet temperature sensor failure
Return water temperature sensor failure
Outlet water temperature too high protection (water cycle heat pump)
Outlet water temperature too low protection (water cycle heat pump)