23
Cable diameter that is calculated according to device capacity and cable length,
residual current device and fuse amper values can be seen at the following table.
Power
(kW)
Phase&Voltage
(V)
Current Drawn
(A)
Fuse&Residual
Current Device (A)
Cable Sections
(mm)
3~400 V 50 Hz Devices
10
3~400
3*15,2
3*20
5*2,5
12
3~400
3*18,2
3*20
5*2,5
16
3~400
3*24,3
3*25
5*4
18
3~400
3*27,3
3*32
5*4
20
3~400
3*30,4
3*40
5*6
24
3~400
3*36,4
3*50
5*6
30
3~400
3*45,5
3*63
5*10
36
3~400
3*54,6
3*63
5*10
40
3~400
3*60,7
3*63
5*16
48
3~400
3*72,8
3*80
5*16
1~220 V 50 Hz Devices
6
1~220
27,3
32
3*4
10
1~220
45,6
50
3*6
12
1~220
54,6
63
3*10
16
1~220
72,8
80
3*16
18
1~220
81,9
100
3*16
Cable sections at this table are calculated for maximum 10 m. Consult your
authorised service for more than 10 m cable length.