background image

 

Status 

Meaning

Fixed ON

iConnector has been supplied with external power

Blinking (4 seconds blink 1

time)

Without external power, iConnector is using battery.

Blinking (2 seconds blink 1

time)

Low battery warning (Used for type D battery version)

Status 

Meaning

Fixed ON

Modbus connected

Blinking (1 seconds blink 2

time)

Connection errors (wrong configuration of baudrate, noise, …)

OFF

No modbus connection

Status 

Meaning

Fixed ON

Connecting with Globiots

Blinking (1s change state)

Initializing wifi generator, waiting for configuration via phone or modbus tool (For

iConnector wifi)

OFF

No connection with Globiots

Address

Size

(bytes)

Memory type

Read/Write

Description

0-0x1FFF

8096

FLASH

R/W

Save active configuration, do not allow log,

realtime.

0x2000-

0x22FF

768

RAM

R

Save data read from modbus slaves.

II. Principle of operation of
iConnector STHC

2.1 General operation principles of
iConnector

2.1.1 LED meaning

2.1.1.1 LED status

2.1.1.2 LED modbus

2.1.1.3 LED network

2.1.2 Memory Map

Summary of Contents for iConnector STHC

Page 1: ...I Specification of iConnector STHC II Principle of operation of iConnector STHC III Offline configuration for iConnector IV Insert SIM Card for Cellular iConnector V Installation iConnector STHC VI Ho...

Page 2: ...eet 2G Nam Hung Vuong Res An Lac Ward Binh Tan Dist Ho Chi Minh City Vietnam Tel 84 28 6268 2523 4 ext 122 Email info daviteq com www daviteq com Distributor in Australia and New Zealand Templogger Pt...

Page 3: ...1900 850 850Japan 900 800Japan standard internal antenna optional external antenna Host Communication Etherner type 01 x RJ45 port 10Mbps Host Communication WiFi type 802 11b g n 2 4Ghz internal ante...

Page 4: ...wall mount cellular version only Operating Temperature Humidity 20 60 degC 95 RH non condensing Housing Protection Aluminum Polycarbonate for Cellular version anti UV plastic for Ethernet WiFi versio...

Page 5: ...nection Status Meaning Fixed ON Connecting with Globiots Blinking 1s change state Initializing wifi generator waiting for configuration via phone or modbus tool For iConnector wifi OFF No connection w...

Page 6: ...aximum for all log cycles Up to 120 log parameters per log cycle Support modbus RTU Address slave 1 247 It is not allowed to set address slave 0 Baudrate 4800 9600 19200 Parity none odd even Up to 100...

Page 7: ...the event configured Supported data types PrmType Description Byte Range 1 BYTE 1 0 to 255 2 UINT16 2 0 to 65 535 3 UINT32 4 0 to 4 294 967 295 4 FLOAT 4 3 40282347 10 38 5 INT16 2 32 768 to 32 767 6...

Page 8: ...s starting Use the iConnector Config Software to connect and configure iConnector Open the 2G 3G tab then fill in the APN information of the SIM Card APN Username Password in Setting Finally click Syn...

Page 9: ...Name Description 2 3 iConnector Ethernet 2 3 1 What is TCP IP 2 3 2 Configure with iConnector Config software Refer to section 5 for more details on how to use Configuration Cable 3 3 2 1 Ethernet tab...

Page 10: ...us TCP Client connected to iConnector role as TCP Server at Static IP address 192 168 1 30 Port 502 in internal network 3 TCP Client sends command to iConnector 4 iConnector transfers commands from Mo...

Page 11: ...t register requested This will be the address on the memmap 0003 The total number of registers requested read 3 registers 40108 to 40110 This number 3 will be 3 bytes not 3 registers anymore At that t...

Page 12: ...to Step 3 Check the Network LED If the LED is always on the connection is successful 2 4 2 Configure using the Configuration Cable Refer to III Offline configuration for iConnector for more details o...

Page 13: ...ation cable has 04 connectors 1st connector is M12 F connector with 4 pin inside A B PWR GND to connect the RS485 port of iConnector 2nd connector is M12 M connector with 4 pin inside A B PWR GND to c...

Page 14: ...please follow these step to install the driver for Window 10 https ftdichip com wp content uploads 2020 08 AN_396 FTDI Drivers Installation Guide for Windows 10 pdf 3 1 2 Offline Configuration Softwa...

Page 15: ...male connector as shown below picture If there is no COM Port please install the driver as abovesection 3 1 3 Select the COM Port associate with the USB port you are connecting with the Configuration...

Page 16: ...ng information APN Username Password Click to the Tab 2G 3G on the Software 3 3 Configuration parameters for iConnector There are many parameters of iConnector to be configured before using However mo...

Page 17: ...server automatically The LED Network will be turn ON Using the provided account of Globiots server log in to the Globiots system to check the status of iConnector If connected the icon will beBlue col...

Page 18: ...END...

Page 19: ...c housing in the vertical direction IV Insert SIM Card for Cellular iConnector Step 1 Remove the housing Step 2 Insert the SIM Card into the iConnector Please take note the direction of the SIM Card T...

Page 20: ...Step 3 Place back the housing and locking by L hex key ATTENTION When reinstalling the cover pay attention to put the PCB edge into the middle slot of the box inside as shown below...

Page 21: ......

Page 22: ...tor of Wireless Bridge must be placed above ground as high as possible not lower than 2m We recommend the minimum is 4m It s better to place the antenna outdoor on top of the roof of building house wa...

Page 23: ...the iConnector at the place has strong coverage of WiFi signal Do not put iConnector inside a metallic box as the WiFi signal can not go thru the metal sheets Incase the iConnector must be place insi...

Page 24: ...es for screwing at the left and right of housing These holes are covered by the cover Open the cover you can access the hole for screwing Using screw with size 4mm diameter maximum 5 3 2 iConnector wi...

Page 25: ...VI How to add iConnector STHC to Globiots Server System...

Page 26: ...VII Modbus Configuration for iConnector STHC on Globiots...

Page 27: ...VIII Parameter Configuration for iConnector STHC on Globiots...

Page 28: ...IX Alarm Event Configuration for iConnector STHC on Glbiots...

Page 29: ...X Configuring special functions of iConnector on Globiots...

Page 30: ...values Check the RF frequency data rate of iConnector and the node 3 Read modbus normal health values but read the data of the node all are 0 The modbus 4 command only supports FW 1 9 old FWs can t re...

Reviews: