background image

4

9

Note:  1.  Long extension leads should be avoided as they often have insufficient 

current carrying capacity to run electric motors, hence they can cause 

substantial voltage drop and operating problems.

 

2.  Minimum voltage at the electric motor must not fall below 216.

 

3.  If the electrical fittings in your country make it necessary to remove the 

plug from the lead fixed to the motor care should be taken to ensure 

that the earth conductor green/yellow in the lead is properly connected 

to a good earth.  This work must only be undertaken by an authorised 

electrician.

Three Phase

Some HM models are also available as 3 phase 

model for 50Hz, nominal 415volt power supply. A 

recommended wiring diagram can be found inside the 

capacitor cover (see figure one below). Three phase 

units must be wired in by an authorised electrician in 

conjunction with a contactor which has “quicktrip” (M10) 

overloads set at nameplate current.

Davey recommend the use of overloads which 

also have the ability to detect “single phasing” 

or “dropped phase” conditions in the power 

supply.

Three phase models with output power of 

below 1.4kW have been designed to provide 

cable entry on the right hand side when viewed 

from the non-drive or fan end of the motor.  A 

terminal block is provided under the capacitor 

cover.  Note: Three phase motors do not have capacitors fitted in the 

capacitor cover.

Access to the terminal block is achieved by removal of the fan cowl 

- see Figure A.  Before prising the fan cowl ensure the retaining screw 

has been removed.

The capacitor cover screw is then removed, allowing the cover to be 

lifted (Figure B).  Once the wiring has been completed and 

checked, ensure the supply cable is run along the cable 

access, the capacitor cover will clamp the supply cable once it 

is re-installed.  Replace the fan cowl and ensure the fan cowl 

retaining screw is re-installed correctly.

Trouble Shooting Check List

MOTOR OPERATING BUT NOT PUMPING

1.  Suction line and pump body not filled with water.

2.  Leaking foot valve.

3.  Air leaks in suction lines or suction pipe not under water.

4.  Air trapped in suction lines (also possible with flooded suction) due to uneven 

rise in piping (eliminate humps and hollows).

5.  No water at source or water level too low.

6.  Valve on suction or delivery lines closed.

MOTOR NOT RUNNING

1.  Power not connected.

2.  Supply voltage too low.

3.  Overload tripped.

4.  Motor not free to turn e.g. a blocked impeller.

5.  Internal motor fault.

MOTOR RUNS FOR SOME TIME THEN STOPS - RESTARTS AUTOMATICALLY 

AFTER SHORT TIME

Overload tripping in motor 

-  low voltage at motor terminals

   

-  motor in direct sunshine or in “hot box”

   

-  motor not free to turn (eg: blocked)

WARNING:

DO NOT RUN DRY.

DO NOT RUN WITH LOSS OF PRIME.

DO NOT PUMP WATER CONTAINING ABRASIVE MATERIALS.

Figure A

Figure B

WARNING:  Automatic reset thermal overloads will allow the pump to restart 

without warning.  ALWAYS disconnect the pump motor from the electrical 

supply before maintenance or repairs.

Reviews: